Item
Data Plan for the
F01D500 Cabinet
Remarks
Number of battery sets: 1 This parameter is set according to the actual
requirements. The number of battery sets can be
set to 0 or 1. That is, the system supports up to one
battery set.
Default value: 1.
Capacity of the battery
set: 75 AH
The battery capacity is configured according to
the actual value. The F02A cabinet uses the 100
AH batteries, the F02AF cabinet uses different
external batteries according to the actual
conditions, the F01D200 cabinet uses the 80 AH
batteries, the F01D500 cabinet uses the 150 AH
or 194 AH batteries, and the F01D1000 cabinet
uses the 150 AH or 194 AH batteries.
Default: 65 AH.
Temperature
compensatio
n parameter
of the battery
Upper temperature
threshold of the battery
set: 80°C
This parameter is set according to the actual
requirements.
Default: 80°C.
Lower temperature
threshold of the battery
set: -20°C
This parameter is set according to the actual
requirements.
Default: -20°C.
Temperature
compensation
coefficient of the battery
set: 80 mV
This parameter is set according to the actual
requirements. The temperature compensation
coefficient refers to the variable of the float
charging voltage of the battery set when the
temperature of the battery set changes by every 1°
C.
Default: 80 mV.
Power
supply load
power-off
and battery
set power-off
parameters
Load power-off
permission status: forbid
This parameter is set according to the actual
requirements.
Default: forbid.
Battery set power-off
permission status: permit
This parameter is set according to the actual
requirements.
Default: permit.
Load power-off voltage:
44 V
This parameter is set according to the actual
requirements.
Default: 44 V.
Battery set power-off
voltage: 43 V
This parameter is set according to the actual
requirements.
Default: 43 V.
UA5000 Universal Access Unit
Environment Monitoring
7 EPS75-4815AF Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
111