Item
Data Plan for the
F01D500 Cabinet
Remarks
Valid level of digital
parameter 1: low level
When the low level represents the valid level, the
host does not report an alarm in the case of low
level.
Digital parameter ID: 3
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the surge protector is set here to
monitor the status of the surge protector. When
the surge protector is faulty, the host reports an
alarm.
Valid level of digital
parameter 3: low level
When the low level represents the valid level, the
host does not report an alarm in the case of low
level.
Digital parameter ID: 5
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the heat exchanger is set here to
monitor the status of the heat exchanger. When
the heat exchanger is faulty, the host reports an
alarm.
Valid level of digital
parameter 5: low level
When the low level represents the valid level, the
host does not report an alarm in the case of low
level.
Digital parameter ID: 6
This digital parameter is set according to the
actual requirements. The digital monitoring
parameter of the MDF door status sensor is set
here to monitor the MDF door status. When the
door of the MDF compartment is open, the host
reports an alarm.
Valid level of digital
parameter 6: low level
When the low level represents the valid level, the
host does not report an alarm in the case of low
level.
Configuration Process
The monitoring parameters can be reported to the control board and the service processing board
only when the data for the ETP4890 is configured correctly in the system.
shows the configuration process, and
lists the commands used during
the configuration.
UA5000 Universal Access Unit
Environment Monitoring
8 ETP4890 Monitoring Solution