Figure 4-1
Direction of heat dissipation
4.1.2 Temperature and Humidity Requirements
To ensure continued safe and reliable equipment operation, install or position the system in a
well-ventilated, climate-controlled environment.
l
Use temperature control devices all year long in any climates.
l
In dry and humid areas, maintain ambient humidity within range with humidifiers and
dehumidifiers respectively.
Table 4-1
Temperature and humidity requirements in the equipment room
Item
Description
Temperature
5ºC to 35ºC (41ºF to 95ºF)
Humidity
8% RH to 90% RH (non-condensing)
4.1.3 Cabinet Requirements
l
A standard 19-inch cabinet with a depth of more than 1000 mm (39.37 in.).
l
Complies with International Electrotechnical Commission 297 (IEC 297).
l
Air filters installed on cabinet doors.
l
AC power supplied from the rear of the cabinet.
4.2 Unpacking the Chassis
Step 1
Check that the packaging is in good condition.