Category
Specifications
Altitude
3050 m (10000 ft.)
NOTE
ASHRAE 2015 compliant:
l
ASHRAE Class A1 and A2 compliant: For altitudes above 900 m
(2952.72 ft.), the highest operating temperature decreases by 1°C
(1.8°F) for every increase of 300 m (984.24 ft.) in altitude.
l
ASHRAE Class A3 compliant: For altitudes above 900 m (2952.72
ft.), the highest operating temperature decreases by 1°C (1.8°F) for
every increase of 175 m (574.15 ft.) in altitude.
l
ASHRAE Class A4 compliant: For altitudes above 900 m (2952.72
ft.), the highest operating temperature decreases by 1°C (1.8°F) for
every increase of 125 m (410.10 ft.) in altitude.
Corrosive gaseous
contaminant
Maximum corrosion product thickness growth rate:
l
Copper corrosion rate test: 300 Å/month (meeting level G1
requirements of the ANSI/ISA-71.04-2013 standard on
gaseous corrosion)
l
Silver corrosion rate test: 200 Å/month
Particle contaminant
l
The equipment room environment meets the requirements
of ISO 14664-1 Class 8.
l
There is no explosive, conductive, magnetic, or corrosive
dust in the equipment room.
NOTE
It is recommended that the particulate pollutants in the equipment room
be monitored by a professional organization.
Acoustic noise
The declared A-weighted sound power levels (LWAd) and
declared average bystander position A-weighted sound
pressure levels (LpAm) listed are measured at 23°C (73.4°F) in
accordance with ISO 7779 (ECMA 74) and declared in
accordance with ISO 9296 (ECMA 109).
l
Idle:
–
LWAd: 6.08 Bels
–
LpAm: 45.2 dBA
l
Operating:
–
LWAd: 7.0 Bels
–
LpAm: 53 dBA
NOTE
Actual sound levels generated during operation vary depending on
server configuration, load, and ambient temperature.
TaiShan 2280 V2 Server
User Guide
13 Product Specifications
Issue 01 (2019-07-01)
Copyright © Huawei Technologies Co., Ltd.
143