400
Series
EN - 33
3. If the RCD does not trip
within the maximum duration
of the test, the instrument
gives a long acoustic signal
which signals the negative
result of the test and then
displays a screen similar to
the one reported here to the
side. Check that the set type
of RCD matches the type of
RCD being tested
R C D
0°
>999ms
FRQ=50.0Hz
Ut=1.4V
VP-N=221V
VP-Pe=221V
TIME NOT OK
The RCD did not trip within the
maximum duration of the test
x1 30mA
50V
Func
IdN RCD UL
4. If the selective RCD trips in a
time lower than the minimum
limit reported in Table 5, the
instrument gives a long
acoustic signal which signals
the negative result of the test
and then displays a screen
similar to the one reported
here to the side. Check that
the set type of RCD matches
the type of RCD being tested
R C D
0°
97ms
FRQ=50.0Hz
Ut=1.4V
VP-N=221V
VP-Pe=221V
TIME NOT OK
The tripping time is not compliant
with Table 5
x1 30mA S
50V
Func
IdN RCD UL
5. If, during a test in mode,
the RCD trips in a time
exceeding the maximum
duration time provided for
the test, the instrument gives
a long acoustic signal which
signals the negative result of
the test and then displays a
screen similar to the one
reported here to the side
R C D
0°
27mA
>
3 0 0 m s
FRQ=50.0Hz
Ut=1.4V
VP-N=228V
VP-Pe=228V
The tripping time is not conform
TIME NOT OK
30mA
50V
Func
IdN RCD UL
6. If, during a test in mode,
the RCD does not trip, the
instrument gives a long
acoustic signal which signals
the negative result of the test
and then displays a screen
similar to the one reported
here to the side
R C D
0°
> 42mA
>
3 0 0 m s
FRQ=50.0Hz
Ut=1.4V
VP-N=228V
VP-Pe=228V
The tripping time is not conform
CURRENT NOT OK
30mA
50V
Func
IdN RCD UL
7.
The results displayed can be saved by pressing the
SAVE
key twice or the
SAVE
key and, subsequently, the
ENTER
key (§ 8.1)