November-2017
Page 40
Press EXIT key to cancel the complete operation.
After entering zone number, zone configuration window appears with its last saved
parameter value.
First configuration is zone name. It is only used for zone identification and will not be
shown on the display. To change it, highlight it with arrow keys and press 0 key. On screen
keyboard will be shown at the top right corner of the display. Working with it is exactly same
as described in changing panel name section.
Second configuration is disabled state of the zone. When zone is disabled, all loop
devices attached to this zone will be in disabled state. It will perform exactly as if it is
disabled from its configuration menu.
To change disabled state, highlight it with arrow keys and press 0 key. If X symbol
appears in front of it, this means that zone is disabled. If X symbol does not appear in front of
it, this means that zone is enabled. If disabled is active, after saving, general disabled LED
will be on.
Number of loop devices attached to the selected zone is displayed on the bottom right
side of the configuration window.
Zone 0 cannot be configured and is always enabled. All on board sounders, relays, aux
powers and input are attached to it.
After finishing updates of configuration, enable key must be on to save the new values.
Press ENTER key. If panel is at access level 3, new data will be saved directly. If panel is at
access level 2, window appears to enter access level 3 password to proceed with saving.