November-2017
Page 32
Third configuration is disabled state of the aux. power. This means that if the aux. power
will be function or not regardless of the current panel state. To change it, highlight it with
arrow keys and press 0 key. If X symbol appears in front of it, this means that the aux. power
will be disabled and not working. If X symbol does not appear in front of it, this means that
the aux. power will be working normally. If disabled is active, after saving, general disabled
LED will be on.
Fourth configuration is delay value. It is used to postpone the aux. power trigger to a
defined amount. The number represents number of half minutes of delay. For example, if
value is 3, so the delay value is 1.5 minutes. If value is 12, so the delay value is 6 minutes.
Minimum value is 0 which means that no delay for this aux. power and it will trigger directly
when at least one of its selected events is active. Maximum value is 14 which mean that
maximum delay is 7 minutes. To change the delay value, highlight it with arrow keys and
directly enter the new delay value. A new small window appears beside the last delay value.
Press ENTER key after entering the new delay value. If value is accepted, it will be shown. If
value is wrong, X symbol appears beside the wrong value. While entering the new delay
value, press EXIT key to cancel entering a new delay value.
Fifth configuration is group number. It is used to activate aux. power only when some
defined input devices are activated. In this case all group parameter for the requested input
devices and aux. power must have the same group number. For example if loop device #5 in
loop 1 and loop device #13 in loop 1 are requested to activate only aux. power 1 when
triggered, then group parameter for the 2 loop devices must be changed from 0 to one group
number (for example 23) and group parameter for aux. power 1 must be changed to 23. There
are maximum 64 groups for whole panel. To change the group value, highlight it with arrow
keys and directly enter the new group value. A new small window appears beside the last
group value. Press ENTER key after entering the new group value. If value is accepted, it will
be shown. If value is wrong, X symbol appears beside the wrong value. While entering the
new group value, press EXIT key to cancel entering a new group value. Note that group 0
means the aux. power will be triggered directly regardless of any grouping in the system
when at least one of its selected events is active.
Sixth configuration is zone number. Zone for on board aux. powers is fixed to zone 0 and
cannot be changed.
After finishing updates of configuration, enable key must be on to save the new values.
Press ENTER key. If panel is at access level 3, new data will be saved directly. If panel is at
access level 2, window appears to enter access level 3 password to proceed with saving.