4.
Input configuration
To select this item use arrow keys to highlight it and press ENTER key or press 4 key
from numeric keypad.
This menu is used to configure all panel onboard dry inputs. You can select any dry input
using arrow key and press ENTER key on the highlighted key or press the key number
directly from numeric keypad. All dry inputs have the same configuration. Only default
settings may be different for some dry inputs.
X Icon in front of a dry input means that this dry input is in disabled state.
After selecting one dry input, dry inputs configuration window appears with its last saved
parameter value.
First configuration is dry input name. It will be displayed on the main screen when this
dry input activates. To change it, highlight it will arrow keys and press 0 key. On screen
keyboard will be shown at the top right corner of the display. Working with it is exactly same
as described in changing panel name section.
Second configuration is which event this dry input will trigger. There are 7 fixed events,
‘Alarm’, ‘Fault, ‘Supervisory’, ‘Pre Alarm’, ‘Silence Alarm’, ‘Re-Sound Alarm’ and ‘Reset’.
To select an event highlight the events field with the arrow keys and press 0 key to select one
event. You can also select none value to make this dry input do nothing. Only one event can
be selected for any input module. Dry inputs are latched when activated. Only fire reset action
deactivates its effect. After fire reset, if dry input is still active, its event will trigger again.
Third configuration is disabled state of the dry input. It means that if the dry input will
trigger its event when activated, or will do nothing whatever is activated or not. To change it,
highlight it with arrow keys and press 0 key. If X symbol appears in front of it, this means
that the dry input will be disabled and not working. If X symbol does not appear in front of it,
this means that the dry input will be working normally. If disabled is active, after saving,
general disabled LED will be on.
Fourth configuration is group number. It is used to activate defined outputs only when
this dry input is activated. In this case all group parameter for this dry input and requested
outputs must have the same group number. For example if dry input 1 needs to activate only
sounder line #1 and relay #3 when triggered, then group parameter for dry input 1 must be
changed from 0 to one group number (for example 33) and group parameter for sounder line