from the on screen keyboard to close it. Press EXIT key to close the on screen keyboard and
return to the current panel name. Maximum characters for panel name are 16 characters. To
save the new panel name, enable key must be turned on. Press ENTER key. If panel is at level
3 access state, new panel name will be saved directly. If panel is at level 1 or level 2 access
states, panel will display level 3 access password window. Enter the 4 level 3 password digits
and press ENTER key.
5.
General configuration
To select this item use arrow keys to highlight it and press ENTER key or press 5 key
from numeric keypad.
This menu is used to change some generic fire alarm related configurations. For each
configuration item, if [X] symbol is displayed, this means that the function is active. If [X]
symbol is not displayed, this means that the function is not active. To change one
configuration item, use arrow keys to highlight it and press 0 key to change its state. Pressing
0 key will toggle [X] symbol in front of highlighted configuration item.
Delete all devices at auto learn: At auto learn, If selected, panel will delete all loop
devices data and starting learning from beginning. If not selected, panel will check
every device ID type. For the same ID, if connected device type is same as saved
device type, panel will keep device configuration as it is. If not same type, panel will
delete the saved one and put the connected one will its default configuration.
Resound on 2
nd
alarm in same zone: When panel is in active fire state and alarm is
silenced. If selected, any new fire from same active zone will trigger the silenced
alarms. If not selected, any new fire from same active zone will not trigger the
silenced alarms.
Bypass output delay on 2
nd
alarm: When panel is in active fire state and output delay
is active for any output devices. If selected, any new fire will cancel the remaining
delayed time and will trigger the delayed output devices. If not selected, any new fire
will keep the delayed output devices off till the delayed time expires.
To save the new configuration items states, enable key must be turned on. Press ENTER
key. If panel is at level 3 access state, new configuration items states will be saved directly. If
panel is at level 1 or level 2 access states, panel will display level 3 access password window.
Enter the 4 level 3 password digits and press ENTER key.