November-2017
Page 36
displays only 50 devices from the loop. To display the remaining IDs, press down arrow key
to show the next 50 devices. IDs are displayed from left to right columns and from up to
down rows. Connected devices ID will be written in its place in the table. IDs not connected
to the loop will not be written in its place in the table. To select device use arrow keys to
highlight it and press ENTER key.
After selecting one device, device configuration window appears with its last saved
parameter value.
Device type is shown at the right side of the name field.
First configuration is device name. For input devices, it will be displayed on the main
screen when this device activates. For output devices, it is only used for reference and cannot
be changed. To change it, highlight it will arrow keys and press 0 key. On screen keyboard
will be shown at the top right corner of the display. Working with it is exactly same as
described in changing panel name section or on board inputs.
Second configuration is events selection. For input devices, it is used to identify which
event this device will trigger. There are 7 fixed events, ‘Alarm’, ‘Fault, ‘Supervisory’, ‘Pre
Alarm’, ‘Silence Alarm’, ‘Re-Sound Alarm’ and ‘Reset’. For output devices, it is used to
identify which events will trigger this device. There are 4 fixed events, ‘Alarm’, ‘Fault,
‘Supervisory’ and ‘Pre Alarm’.
For input devices, to select an event highlight the events field with the arrow keys and
press 0 key to select one event. You can also select none value to make this device do
nothing. Only one event can be selected for any device. Devices are latched when activated.
Only fire reset action deactivates its effect. After fire reset, if devices is still active, its event
will trigger again. For all detectors, alarm event is selected by default and cannot be changed.
For output devices, to make the device triggers or does not trigger on one event, highlight
it with arrow key and press 0 key. If X symbol appears in front of the event, this means that
the device will trigger on this event. If X symbol does not appear in front of the event, this
means that the device will not trigger on this event. Selection of more than one event is
accepted.
Third and fourth configurations are day and night sensitivities for photoelectric some
detectors. 3 levels are defined, 'Low', 'Medium' and 'High'. To change selection, press 0 key.