November-2017
Page 15
Access level 3 is the highest secure level and is protected by password. Added to access
level 1 & 2 permissions, it has the ability to change any panel configuration data and it has
access to 4
th
sub menu which contains advanced panel operations.
To make changes to any panel configuration data, with level 3 access, enable key must be
turned on to proceed saving any changes.
Access level 2 & 3 passwords and enable key must only be known and kept to the
identified persons who have the permissions to perform different panel functions.
5.2.
Panel states
HST-HP201-2AB has 7 different panel states.
Init & Stop state: This panel mode is valid at power up while panel is intializing its
modules and when panel is doing restore for all its default data. Any alarm, fault or
supervisory conditions will happen in this phase will be ingnored by the panel.
Learn state: This panel mode is valid at learning phase after power up or when loops
auto learn is requested from programming menus. Only loops fault and loop devices
fault will be triggered after learning is finsihed. Any other alarm, fault or supervisry
conditions will be ignored.
PC state: This panel mode is valid when computer software starts to update part or all
of panel configuration data. Panel will not enter PC mode if it has one or more alarm
conditions. If panel has one or more fault conditions, it will do automatically fire
reset. Any new alarm, fault or supervisory conditions will be ignored by the panel.
LCD displays PC mode window. Panel will restart itself after computer software
finishes its update within the panel.