3.
Add device
To select this item use arrow keys to highlight it and press ENTER key or press 3 key from
numeric keypad.
It is used to manually add loop devices to the registered loop devices in the panel.
First you select the loop number, and then small window will appear to enter loop device ID
and its type.
Use up and down arrow keys to move between ID and type fields.
For ID field, enter the loop device ID which is needed to be added to the loop from numeric
keypad.
For type field, press 0 key to selected the device ID type.
Press ENTER key to continue. If there is an already loop device registered with this ID,
message is displayed informing that this ID is already registered to this loop. If this ID is not
registered, then loop device configuration window appears with this ID and type. This
window is exactly same as normal device configuration window and user can modify it
exactly same as described in device configuration window for input and output loop devices.
After finishing updates of configuration, enable key must be on to save the new values. Press
ENTER key. If panel is at access level 3, new data will be saved directly. If panel is at access
level 2, window appears to enter access level 3 password to proceed with saving.