November-2017
Page 14
After learning, panel displays its main window. Date & time are displayed at the upper
left part of the LCD. Logo and panel model are displayed at the upper right part of the LCD.
Panel name and current status are displayed down to date and time information.
First alarm is displayed at middle of LCD. Number of current alarm, fault and supervisory
conditions are displayed down to first alarm section. Last row in the LCD is used to display
some icons which identify some information about panel current status.
LCD backlight is on by default. In case of no updates on LCD (except date & time), LCD
backlight will be turned off after 5 minutes. LCD backlight can be turned on again with any
change on LCD.
5.1.
Access levels
HST-HP201-2AB has 3 access levels for different panel operations from panel users.
Access level 1 is the least secure level and has no protected password. It is the default
level after power on and it has the ability to see different alarm and fault information at the
main screen and it can silence panel buzzer.
Access level 2 is the medium secure level and it is protected by password. Added to
access level 1 permissions, at alarm, fault or supervisory conditions, it has the ability to
silence the trigged alarms, re-sound the silenced alarm, and perform fire reset. Also it can
trigger Evacuate key on the panel.
Access level 2 users can also access panel programming & configuration menus through
Menu key on the panel. Users can only see all panel configuration data but they cannot make
any changes to it.