Appendix A Parameters
Shenzhen Hpmont Technology Co., Ltd.
―
84
―
HD31 Series User Manual V1.1
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
F19: Function-boost Parameters , on pages 45 - 47
F19.07 Fan
control
0: Auto stop
1: Immediate stop
2: Runs all the time when power
on
0 1
○
F19.08
Fan control delay time
0.0 - 600.0s
30.0s
0.1s
○
F19.16
Restart after power failure
0: Disabled
1: Enabled
0 1
×
F19.17
Delay time for restart
after power failure
0.00 - 10.00s
2.00s
0.01s
○
F19.18 Stall
overvoltage
0: Disabled
1: Enabled
1 1
×
F19.19
Stall overvoltage point
0 - 1200V
740V
1V
×
F19.20
Auto current limit
0: Disabled
1: Enabled in Acc / Dec running
process, but disabled in
constant speed runnng process
2: Enabled both in Acc / Dec and
constant speed running process
1 1
×
F19.21
Auto current limit
threshold
20.0 - 200.0%
110.0%
0.1%
×
F19.22
Dec time at auto current
limit
0.0 - 6000.0s
0.00: Limit current without Dec
18.5kW and
below:10.0s
22 - 75
kW: 30.0s
90kW and
above: 60.0s
0.1s
×
F19.23
Enabled terminal at
power on
0: Rise edge
1: Level
0 1
○
F19.24
Action voltage of braking
unit
630 - 750V
720V
1V
×
F20: Fault Protection Parameters, on pages 47 - 50
F20.00
Overload pre-alarm
detection
Units: Overload pre-alarm
detection
0: It is active all the time in
running status
1: It is active only at constant
speed
Tens: Overload pre-alarm action
0: HD31 doesn’t alarm and
continues running
1: HD31 alarms and stops
running
00000 1
×