Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
―
62
―
HD31 Series User Manual V1.1
Ref. Code
Name Description
Setting Range [Default]
P05.03
Pressure sensor range setting
0.0 - 10.0 [1.6MPa]
1MPa=10kg/cm
2
.
P05.04
Pressure sensor signal type selection
0 - 2 [0]
0: 0 - 10V.
1: 0 - 20mA.
2: 4 - 20mA.
Note:
1. Only the AI2, AI3, AI4 terminals can be input the current signal and need to change the CN6 of the control
board or the CN2 or CN3 jumper on water supply card. Please refer to the jumper description in the user manual
for details.
2. When P05.04 = 2, set the F05.00 teb bit to 1 and set F05.05 = 20.0%. When P05.04 = 0 or 1, set F05.00 ten bit to
0 and set to F05. 05 = 0.0%.
P05.05
Water supply method selection
0x00 - 0x75 [0x00]
Modify P05.05 and system will automatically set P01.00 - P01.06, P03.15 - P03.24. Set the principle:
Follow P01.00 - P01.06 to set the frequency conversion / power frequency pump, set P03.16 - P03.24,
P03.15 power and variable frequency control in turns.
For example
: Set P05.05 = 0x24, the parameters automatically set, as follows:
Ref. Code
Function
Value
Defination
P01.00
Pump 1 type
1
Pump 1 is
variable
frequency
pump
P01.01
Pump 2 type
1
Pump 2 is
variable
frequency
pump
P01.02
Pump 3 type
1
Pump 3 is
variable
frequency
pump
P01.03
Pump 4 type
1
Pump 4 is
variable
frequency
pump
P01.04
Pump 5 type
2
Pump 5 is power frequency pump
P01.05
Pump 6 type
2
Pump 6 is power frequency pump
P01.06
Pump 7 type
0
Invalid
P03.15
RLY1 function
12
Pump 6 power frequency running
P03.16
RLY2 function
1
Pump 1 variable frequency running
P03.17
RLY3 function
2
Pump 1 power frequency running
P03.18
RLY4 function
3
Pump 2 variable frequency running
P03.19
RLY5 function
4
Pump 2 power frequency running
P03.20
RLY6 function
5
Pump 3 variable frequency running
P03.21
RLY7 function
6
Pump 3 power frequency running
P03.22
RLY8 function
7
Pump 4 variable frequency running
P03.23
RLY9 function
8
Pump 4 power frequency running
P03.24
RLY10 function
10
Pump 5 power frequency running
Note:
1. A bit indicates the number of variable frequency pumps in the system; ten indicates the number of frequency
pumps in the system.
2. The number of frequency pump plus frequency pump can not exceed 7, the total number of relays can not be
more than 10.