Shenzhen Hpmont Technology Co., Ltd.
Appendix A Parameters
HD31 Series User Manual V1.1
―
91
―
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
P01.02
Pump 3 type
2: Power frequency pump
3: Dormant pump
4: Sewage pump
0 1
×
P01.03
Pump 4 type
0
1
×
P01.04
Pump 5 type
0
1
×
P01.05
Pump 6 type
0
1
×
P01.06
Pump 7 type
0
1
×
P01.07
Rated current of pump 1
7.5kW above motor: 0.1 - 999.9A
depend on
motor
0.1A
×
7.5kW and below motor: 0.01 -
99.99A
0.01A
P01.08
Rated current of pump 2
7.5kW and above motor: 0.1 -
999.9A
0.1A
×
7.5kW and below motor: 0.01 -
99.99A
0.01A
P01.09
Rated current of pump 3
7.5kW above motor: 0.1 - 999.9A
0.1A
×
7.5kW and below motor: 0.01 -
99.99A
0.01A
P01.10
Rated current of pump 4
7.5kW above motor: 0.1 - 999.9A
0.1A
×
7.5kW and below motor: 0.01 -
99.99A
0.01A
P01.11
Ratedcurrent of pump 5
7.5kW above motor: 0.1 - 999.9A
0.1A
×
7.5kW and below motor: 0.01 -
99.99A
0.01A
P01.12
Rated current of pump 6
7.5kW above motor: 0.1 - 999.9A
0.1A
×
7.5kW and below motor: 0.01 -
99.99A
0.01A
P01.13
Ratedcurrent of pump 7
7.5kW above motor: 0.1 - 999.9A
0.1A
×
7.5kW and below motor: 0.01 -
99.99A
0.01A
P02: Water Supply PID Parameter, on pages 57 - 59
P02.00
Pressure setting source
0: Digital setting
1: Pressure setting of timing
water supply
2: Pressure setting of analogue
water supply
0 1
×
P02.01
Pressure digital setting
0.0 - P05.0 3×10 kg/cm
2
0.0
kg/cm
2
0.10kg/cm
2
×
P02.02
Pressure time
1 - 12
1
1
×
P02.03
T1 start time
00.00 - 23.59
00.00
0.01
×
P02.04
T1 time pressure
0.0 - P05.0 3×10 kg/cm
2
0.0
kg/cm
2
0.10kg/cm
2
×
P02.05
T2 start time
00.00 - 23.59
00.00
0.01
×
P02.06
T2 time pressure
0.0 - P05.0 3×10 kg/cm
2
0.0
kg/cm
2
0.10kg/cm
2
×
P02.07
T3 start time
00.00 - 23.59
00.00
0.01
×
P02.08
T3 time pressure
0.0 - P05.0 3×10 kg/cm
2
0.0
kg/cm
2
0.10kg/cm
2
×
P02.09
T4 start time
00.00 - 23.59
00.00
0.01
×
P02.10
T4 time pressure
0.0 - P05.0 3×10 kg/cm
2
0.0
kg/cm
2
0.10kg/cm
2
×
A