Chapter 6 Function Introduction
HD31 Series User Manual V1.1
―
43
―
6.2.9
F17: SCI Communication Parameters
Ref. Code
Function Description
Setting Range [Default]
F17.00 Data
format
0 - 5 [0]
0: 1-8-2 format, no parity, RTU.
1: 1-8-1 format, even parity, RTU.
2: 1-8-1 format, odd parity, RTU.
3: 1-7-2 format, no parity, ASCII.
4: 1-7-1 format, even parity, ASCII.
5: 1-7-1 format, odd parity, ASCII.
F17.01 Baud
rate
0 - 5 [3]
0:
1200bps.
1: 2400bps.
2: 4800bps.
3: 9600bps.
4: 19200bps
5: 38400bps.
F17.02 Local
address
0 - 247 [2]
F17.02 = 0, it means broadcast address.
F17.03
Host PC response time
0 - 1000 [0ms]
F17.04
Detection time at communication timeout
0.0 - 1000.0 [0.0s]
Time at no communication data > setting time of F17.04, it will be considered as E0028 fault (SCI timeout
fault).
•
F17.04 = 0, it will not detect communication timeout.
F17.05
Detection time at communication error
0.0 - 1000.0 [0.0s]
Time at communication error > setting time of F17.05, it will be considered as E0029 fault (SCI error).
•
When F17.05 = 0, it will not detect the communication error.
F17.06
Action selection at communication timeout
0 - 3 [3]
F17.07
Action selection at communication error
0 - 3 [3]
F17.08
Action selection at communication peripheral device fault
0 - 3 [1]
F17.06 defines the action selection at commmunication timeout.
F17.07 defines the action selection at communication error.
In the communication command setting mode, F17.08 will define the action selection when
communication peripheral device fault is alarmed.
0: Coast to stop.
1: Emergency stop.
2: Decelerate to stop.
3: Continue to run.