Shenzhen Hpmont Technology Co., Ltd.
Appendix A Parameters
HD31 Series User Manual V1.1
―
81
―
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
detection threshold
F15.29
Zero-frequency hysteresis
0.00 - upper limit
0.00Hz
0.01Hz
○
F16: Analogue I/O Terminal Parameters, on pages 41 - 43
F16.00
Keypad with
potentiometer function
0: Unused
1: Upper limit frequency setting
2: Frequency setting
0 1
×
F16.01 AI1
function
2
1
×
F16.02 AI2
function
0
1
×
F16.03 AI3
function
0
1
×
F16.04 AI4
function
0
1
×
F16.05
AI1 bias
-100.0 - 100.0%
0.0%
0.1%
○
F16.08
AI2 bias
-100.0 - 100.0%
0.0%
0.1%
○
F16.11
AI3 bias
-100.0 - 100.0%
0.0%
0.1%
○
F16.14
AI4 bias
-100.0 - 100.0%
0.0%
0.1%
○
F16.06
AI1 gain
-10.00 - 10.00
1.00
0.01
○
F16.09
AI2 gain
-10.00 - 10.00
1.00
0.01
○
F16.12
AI3 gain
-10.00 - 10.00
1.00
0.01
○
F16.15
AI4 gain
-10.00 - 10.00
1.00
0.01
○
F16.07
AI1 filtering time
0.01 - 10.00s
0.05s
0.01s
○
F16.10
AI2 filtering time
0.01 - 10.00s
0.05s
0.01s
○
F16.13
AI3 filtering time
0.01 - 10.00s
0.05s
0.01s
○
F16.16
AI4 filtering time
0.01 - 10.00s
0.05s
0.01s
○
F16.17
Max. input pulse
frequency
0.0 - 50.0kHz
10.0kHz
0.1kHz
○
F16.18
Input pulse filter time
0 - 500ms
10ms
1ms
○
F16.19 AO1
function
0, 6 - 9: Unused
1: Output frequency (0 - max.
output frequency)
2: Setting frquency (0 - max.
output frequency)
3: Motor RPM (0 - max. output
frequency corresponding to
RPM)
4: Output current (0 - twice
rated current of motor)
5: Output current (0 - twice
rated current of motor)
10: Output torque (0 - 3 times
rated torque of motor)
11: Output voltage (0 - 1.2 times
rated voltage of HD31)
12: Bus voltage (0 - 2.2 times
rated voltage of HD31)
1 1
○
F16.20 AO2
function
0
1
○
A