Appendix A Parameters
HD31 Series User Manual V1.1
―
73
―
Appendix A
Parameters
Attributes are changed:
“X”: It denotes that the setting of this parameter cannot be modified when HD31 is in run status.
“O”: It denotes that the setting of this parameter can be modified when HD31 is in run status.
“*”: It denotes that the value of this parameter is the actual value which cannot be modified.
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
d00: Status Display Parameters, on pages 26 - 29
d00.00
Inverter series
0x10 - 0x50
*
d00.01
Software version of the
control board
00.00 - 99.99
*
d00.03
Special software version
of the control board
00.00 - 99.99
*
d00.05
Software version of the
keypad
00.00 - 99.99
*
d00.06
Customized series No.
0 - 9999
*
d00.08
Rated current of the
inverter
7.5kW and below: 0.01A
11kW and above: 0.1A
*
d00.09
Extended function of the
inverter
0: No extended function
1: Constant pressure water
supply function
*
d00.10 Inverter
status
Bit0: Inverter fault
Bit1: Run / stop
Bit2: Forward / reverse
Bit3: Zero speed running
Bit5&Bit4: Acc / Dec / Constant
Bit6: Unused
Bit7: DC braking
Bit8: Auto-tuning
Bit9: Unused
Bit10: Speed limit value
Bit11: Unused
Bit12: Stall overvoltage
Bit13: Current limit
Bit14, Bit15: Unused
*
d00.14
Setting frequency
0.01 - 400.00Hz
*
d00.15
Setting frequency (after
Acc / Dec)
0.01 - 400.00Hz
*
d00.16
Output frequency
0.01 - 400.00Hz
*
d00.17
Setting RPM
0 - 60000rpm
*
d00.18
Running RPM
0 - 60000rpm
*
d00.19
Three-phase power
supply input sequence
phase
0: Positive sequence, L1(R)
preceding L2(S) preceding L3(T)
1: Negative sequence, L1(R)
preceding L3(T) preceding L2(S)
*
A