![HP HPE 3PAR StoreServ 8000 Скачать руководство пользователя страница 81](http://html.mh-extra.com/html/hp/hpe-3par-storeserv-8000/hpe-3par-storeserv-8000_installation-manual_165481081.webp)
Cabling the Service Processor
1.
Connect a customer-supplied Ethernet cable to the lowest port on the server and keep the
other end of the Ethernet cable disconnected.
2.
Connect the power cable to PDU, but
do not
power on at this point.
WARNING!
Do not power on the SP without completing the remainder of the physical
installation.
The following icon is typical, but it can vary by server.
Figure 80 Connection icon
Cabling Power to the System
WARNING!
Before you begin cabling the power cords, verify that your power connections are
set up correctly. See
“Verifying Power Connections” (page 83)
When routing PCM power cords, ensure that power redundancy is maintained by connecting
each PCM within a shelf to a different PDU. When observed from the rear, the left side cabling
(ID #0) is black, and the right side cabling (ID #1) is gray.
WARNING!
The PCM latch can damage any cables that are routed in such a way that when
the PCM latch handle is closed, it will cut into any cable that becomes wedged between the latch
and the rack post. Keep the cables clear from the PCM latch mechanism.
NOTE:
When installing cabling, ensure clear access to all system components. All power cords
need to be tied and kept behind the rail column in order to access the components during servicing.
To cable the power cables:
1.
Locate the power cord for each PCM.
NOTE:
Before inserting the power cords into the PCMs, verify that the PCM power switch
is set to 0 (off).
2.
Route the main power cords to a power strip or PDU. Ensure that the routed cords maintain
proper service clearance.
3.
Insert each end of the power cord into the power strip/PDU and PCM. Fasten the PCM power
cord using the restraining clip on each PCM.
NOTE:
Do not power on the PCMs at this time.
Cabling the Service Processor
81
Содержание HPE 3PAR StoreServ 8000
Страница 52: ...3 Install the cage nuts Figure 50 Cage nut installation 52 Power Distribution Unit Installation ...
Страница 53: ...4 Install the PDU Figure 51 1U PDU installation Figure 52 0U PDU installation Installing 1U and 0U PDUs 53 ...
Страница 117: ...Battery for 764 W PCM 764 W PCM without Battery 580 W PCM 3 5 inch LFF Drive 2 5 inch SFF Drive System Components 117 ...
Страница 132: ...Workaround Close the browser and relaunch the Service Processor IP Setup wizard 132 Troubleshooting ...
Страница 142: ...142 Warranty and regulatory information ...
Страница 143: ...Regulatory Information 143 ...