Ground Bonding kit 51
4.
Insert a T-25 Torx screw through the other end of the same grounding strap, and then insert the screw
in the hole on the rack front door. Tighten the screw.
For front doors (with a grounding lug):
1.
Insert a T-25 Torx screw through the other grounding strap end and secure it to the front door.
2.
Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the front door,
and then tighten the washer.
From the system chassis rail to the right rear door:
1.
Insert a T-25 Torx screw through the end of a 36.83-cm (14.5-inch) grounding strap, and then secure
the screw to the system chassis rail.
2.
Place the other end of the same grounding strap over the grounding lug on the right rear door.
3.
Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the right rear
door, and then tighten the washer.