background image

22

4 205 254 / 03

Commissioning

The  following  systems  must  be  equipped  with 
separate circuits:

Systems with a specific water content of over 50 

• 

ltr./kW for the boiler (in cascades, for the smallest 
boiler)

Plants with 

• 
  - 

continuous 

oxygen intake (e.g. underfloor heat-

ing systems without diffusion proof plastic piping 
or open expansion tank) or 

  - 

intermittent

 oxygen intake (e.g. where frequent 

refilling is necessary)

Older systems with formation of sludge in which in-

• 

creased concentrations of the metals which come 
into contact with the water are found in the existing 
heating water.
Systems operated with softened water.

• 

Treated heating water must be tested at least 1x 

• 

yearly,  according  to  the  inhibitor  manufacturer‘s 
instructions, more frequent testing may be neces-
sary.

A refilling is not necessary if the quality of the heat-

• 

ing water in existing installations (e.g. exchange of 
boiler)  conforms  to VDI  2035. The  Directive VDI 
2035 applies equally to the replacement water.

New  and  if  applicable  existing  installations  must 

• 

be  adequately  cleaned  and  flushed  before  being 
recharged! The boiler may only be filled after the 
heat ing system has been flushed. 

Parts of the boiler which have contact with water 

• 

are made of aluminium.

On  account  of  the  danger  of  spot  corrosion  the 

• 

chloride, nitrate and sulfate contents of the heat-
ing water must not exceed 200 mg/l in total.

The pH value of the heating water should lie be-

• 

tween  8,0  and  8,5  after  6  -  12  weeks  of  heating 
operation.

Filling and replacement water

4.3 

For a plant using Hoval boilers untreated drinking 

• 

water is generally best suited as fil ling and replace-
ment water. However, the quality of the untreated 
drinking water must at least fulfil the standard set 
in VDI  2035  or  be  desalinated  and/or  be  treat ed 
with inhibitors. The stipulations of EN 14868 must 
be observed.

In order to maintain a high level of boiler ef ficiency 

• 

and to avoid overheating of the heati ng surfaces 
the values given in the 

table 1

 should not be ex-

ceeded (dependent on boil er performance ratings 
- for multi-boiler plants rating of smallest boiler ap-
plies - and on the water content of the plant).

The total amount of filling and replacement water 

• 

which  is  used  throughout  the  total  ser vice  life  of 
the boiler must not exceed three times the water 
capacity of the plant.

Boilers with aluminum: generally inhibitors may be 

• 

filled in only by a specialized company. 

If a reduction in water hardness is necessary we 

• 

recommend a complete desalination (softening is 
not appropriate). Residual tap water might remain 
in  the  plant  as  a  result  of  the  preceding  flushing 
process, entailing an increase in the sum of alka-
line-earths  to  approx.  0,5  mol/m

3

.  During  the  fill-

ing procedure the conductance of the filling water 
should  be  supervised. This  should  be  to  approx. 
100 µS/cm .

After  filling  the  conductance  of  the  plant  water 

• 

should be between 50 and 200 µS/cm. The pH val-

ue will adjust itself thereby from 
initially  6,5  -  7,5  after  some 
weeks been in use on 8,0 - 8,5. 
If this should not be the case, 
then  specialized  company  for 
the  water  treatment  is  to  be 
assigned.  This  compa ny  must 
as  soon  as  the  adjustment  of 
the cor rect pH value has been 
completed by inhibitors, which 
are suitable for aluminium ma-
terials also regularly check the 
inhibitor concentration and the 
pH value.

Table 1

Maximum filling capacity based on VDI 2035

Available for boiler with < 0,3l/kW water capacity

Total hardness of the filling water up to ...

[mol/m

3

1

<0,1

0,5

1

1,5

2

2,5

3

>3,0

f°H

<1

5

10

15

20

25

30

>30

d°H

<0,56

2,8

5,6

8,4

11,2

14,0

16,8

>16,8

e°H

<0,71

3,6

7,1

10,7

14,2

17,8

21,3

>21,3

~mg/l

<10

50,0

100,0

150,0

200,0

250,0

300,0

>300

Conductance 

2

<20

100,0

200,0

300,0

400,0

500,0

600,0

>600

boiler size of the 
individual boiler

maximum filling quantity without desalination

30 to 50 kW

NO DEMAND

50 l/kW 50 l/kW 20 l/kW 20 l/kW 20 l/kW

50 to 200 kW

50 l/kW 20 l/kW 20 l/kW

always desalinate

1

total of alkaline earths

2

 If the conductance in µS/cm exceeds the tabular value an analysis of the water is necessary.

Содержание TopGas 30

Страница 1: ...g boiler TopGas 30 35 45 50 60 for natural and liquid gas Wall mounted gas boilers TopGas 30 35 45 50 60 according to DIN 4702 DIN EN 483 and DIN EN 677 are suitable and approved as heat producers for...

Страница 2: ...ydraulic connection 15 3 4 1 Protection planning guidelines for the hydraulic connection 15 3 4 2 Boil dry safeguard 15 3 4 3 Gravity brake 15 3 4 4 Minimum flow rate 15 3 4 5 To be provided by custom...

Страница 3: ...ng 23 4 3 7 Setting the gas flow rate CO2 O2 and measurement of NOx CO content in the flue gas flue gas measurement 23 4 3 8 Changing to a different kind of gas 24 4 4 Handing over to the user 25 4 4...

Страница 4: ...r instructions are enclosed with the individually packed components Adjustment Accessories Further information sources Hoval catalogue Standards regulations Safety instructions 1 4 When working on the...

Страница 5: ...on and scale formation in hot water heating systems Firing regulation for the Federal regions DVGW TRGI 86 96 Technical regulations of gas supply enterprises VDE 0100 for electrical installations and...

Страница 6: ...R 3 4 R 3 4 R 3 4 R 3 4 Air flue gas mm C80 125 C80 125 C80 125 C80 125 C80 125 Gas flow pressure min max Natural gas E LL mbar 18 50 18 50 18 50 18 50 18 50 Liquid gas mbar 42 57 42 57 42 57 42 57 4...

Страница 7: ...on the utilised flue gas pipeline system In the front 500 mm 1 Gas connection R 2 Heating flow Rp 1 3 Heating return Rp 1 4 Condensate drain 32 5 LAS flue gas supply air connection DN 80 125 View fro...

Страница 8: ...llective electrode for ignition and flame guide Ionisation Main gas valve ev LPG valve heating room ventilation accessable Water side resistance mbar Flow rate m3 h 0 50 100 150 200 250 300 350 400 45...

Страница 9: ...display option Function Mode indication Parameter Indication Value indication Meaning Description Standby Mode Normal position Start position current flow temperature no indication 0 Standby no heat...

Страница 10: ...Mode indication Parameter Indication Value indication Meaning Description Informations Mode It is possible to read monetary values from here Point is blinking 0 e g 45 Current flow temperature Heatin...

Страница 11: ...sends a reference value to the firing device this value is limited by the value set using parameter 18 Parameter 19 2BI Minimum outside temperature 19 2BI Minimum outside temperature This parameter d...

Страница 12: ...s valve or a combustion chamber ventilator is installed Parameter 62 2GG DHW charging switch pump This parameter is used to indicate whether a separate pump is present for DHW charging or there is sim...

Страница 13: ...pipeline system Diaphragm expansion tank 3 1 1 Depending on the hydraulic situation of the system an adequately dimensioned diaphragm expansion tank with an inlet pressure of at least 0 3 bar above th...

Страница 14: ...ng window 2 Fan 3 Flue gas air inlet 4 Water pressure deflector 5 Flue gas temperature sensor 6 Flow temperature sensor 7 Return temperature sensor 8 Ignition ionisation electrode 9 Heat exchanger 10...

Страница 15: ...umen tation When modernising an old heating system with an open expansion tank this is to be converted to a closed heating system with a diaphragm expansion tank and safety valve Protection planning g...

Страница 16: ...pe Sie haben die M glichkeit ein neues Shape zu nehmen hovhovalhovalhoval hovalhovalhovalhov P TopGas 30 60 PLP ZUP M 5 T T DKP T T DKP T T SLP Dies ist ein unerlaubter Weg Gehen Sie einen Schritt zur...

Страница 17: ...the flue gas extrac tion with heat output gas boilers Waste gas pipelines in compliance 3 5 1 with building construction law The flue gases from the Hoval TopGas 30 35 45 50 60 can be removed via a ga...

Страница 18: ...For the vertical supporting of the chimney pipeline the very bot tom element must be permanently fixed mounting rail or pipe clip Horizontal connections must have a gradient of at least 5 cm per runni...

Страница 19: ...rennungsluft If necessary an inspection T piece has to be inserted Combustion air TopGas Falls erforderlich ist ein Inspektions T St ck einzusetzen Verbrennungsluft If necessary an inspection T piece...

Страница 20: ...ulations of gas supply enterprises should be observed A manually operated shut off device gas shut off cock in accordance with the local regulations is to be installed directly before the boiler Pleas...

Страница 21: ...are to be complied with for the electrical installation and com missioning Automatic firing units are safety devices and are not to be opened Boiler control 3 6 3 electrical connection diagram The el...

Страница 22: ...f the heati ng surfaces the values given in the table 1 should not be ex ceeded dependent on boil er performance ratings for multi boiler plants rating of smallest boiler ap plies and on the water con...

Страница 23: ...be checked during measuring at the boiler site Bleeding the gas pipeline 4 3 3 Open the gas shut off value and bleed the air from the pipeline up to the gas fitting comply with the relevant regulatio...

Страница 24: ...eration calorific value HuB is needed Ask your gas utility for it The setting value is calculated as followed Heat load NB Setting value Operation Calorific value HuB kW m3 NB x 1000 l HuB 60 min The...

Страница 25: ...urner heating controller etc and is consequently sufficiently familiar with the system A pre printed form in duplicate for this confirma tion is to be found on last page of these installation instruct...

Страница 26: ...move the front boiler panel open the control flap lid push the front cover upwards and pull out Unscrew the threaded of the supply pipeline to the gas solenoid valve picture 6 4 1 see next page Detach...

Страница 27: ...27 4 205 254 03 Maintenance Picture 6 4 1 Picture 6 4 2 Gas screw connection Bolting Burner plate Picture 6 4 3...

Страница 28: ...If the defined gradient limiting curve parameter 15 2BE is exceeded a blocking is caused Before the blocking occurs the speed is minimised There is also a limiting curve existing parameter 16 2BF P 26...

Страница 29: ...gher than 100 C by the return sensor occurs a locking E 06 Return sensor interruption If the temperature is lower than 20 C the return sensor seems as disconnected and responds with a lock ing E 07 Fl...

Страница 30: ...Internal fault in the automatic firing unit E 17 Flow Return 45K f r 10 Sek If the difference between the flow temperature and return temperature is higher than 45K for more than 10 seconds during a h...

Страница 31: ...eating operation 1 C OEM 10 13 P2BC proportional value in heating operation mode 1 C OEM 15 14 P2BD integration time in heating operation mode 1s OEM 20 15 P2BE maximum gradient for flow temperature b...

Страница 32: ...2 1 OEM 36 50 P2FE interval 3 1s OEM 30 51 P2FF maximum output during interval 3 1 OEM 52 52 P2FG interval 4 1s OEM 30 53 P2FH maximum output during interval 4 1 OEM 68 54 P2FI interval 5 1s OEM 30 55...

Страница 33: ...33 4 205 254 03...

Страница 34: ...tallation Place Date Installation address Type Ser No Year of manufacture System installer System user Copy for plant user C O N F I R M AT I O N The user owner of the system herewith confirms that he...

Отзывы: