Technical details
Technical details
2.
Technical Data
2.1
Typ
(30)
(35)
(45)
(50)
(60)
• Rated heating capacity 80/60°C with natural ga
1
kW
6,0-27,4
6,0-31,8
10,0-41,0 11,7-48,3 11,7-55,3
• Rated heating capacity 40/30°C with natural gas
1
kW
6,8-30,1
6,8-35,0
11,1-45,0 12,8-52,9 12,8-60,7
• Rated heating capacity 80/60°C with propane gas
3
kW
6,2-27,4
6,2-31,9
10,8-41,0 13,1-47,8 13,1-54,9
• Rated heating capacity 40/30°C with propane gas
3
kW
7,0-30,2
7,0-35,2
11,9-45,0 14,1-52,5 14,1-60,3
• Rated thermal loading with natural gas
1
kW
6,4-28,3
6,4-33,0
10,6-42,5 12,2-49,9 12,2-57,3
• Rated thermal loading with propane gas
3
kW
6,6-28,5
6,6-33,2
11,4-42,5 13,6-49,6 13,6-56,9
• Operating pressure, heating max./min.
bar
3,0 / 1,0
3,0 / 1,0
3,0 / 1,0
3,0 / 1,0
3,0 / 1,0
• Operating temperature max.
°C
85
85
85
85
85
• Boiler water contents
l
4,5
4,5
4,5
6,0
6,0
• Minimum water circulation quantity
l/h
300
300
350
470
470
• Boiler weight (without water content, incl. body)
kg
83
83
83
89
89
• Standard level of utilization
40/30°C
%
109,8
109,7
109,3
109,7
109,5
75/60°C
%
106,3
106,1
105,8
105,8
105,6
• Standby heat losses at 70°C
Watt
92
92
95
115
115
• Standard emission factors
Nitrous oxide
mg/kWh
30,2
30,2
30,2
35,0
35,0
Carbon dioxide
mg/kWh
9,0
9,0
11,2
13,0
13,0
• CO
2
content in flue gas max./min. capacity
%
9,0 / 8,8
9,0 / 8,8
9,0 / 8,8
9,0-8,8
9,0 / 8,8
• Dimensions
See dimension sheet
• Connections
Flow / Return
Zoll
Rp 1 1/4" Rp 1 1/4"
Rp 1 1/4"
Rp 1 1/4"
Rp 1 1/4"
Gas
Zoll
R 3/4"
R 3/4"
R 3/4"
R 3/4"
R 3/4"
Air / flue gas
Ø
mm
C80/125
C80/125
C80/125
C80/125
C80/125
• Gas flow pressure min./ max.
Natural gas E/LL
mbar
18-50
18-50
18-50
18-50
18-50
Liquid gas
mbar
42-57
42-57
42-57
42-57
42-57
• Gas connection values at 0°C / 1013 mbar:
Natural gas E - (Wo = 15,0 kWh/m
3
) Hu = 9,97
m
3
/h
2,83
3,3
4,3
1,2-5,8
5,8
Natural gas LL- (Wo = 12,4 kWh/m
3
) Hu = 8,57
m
3
/h
2,84
3,9
5,0
1,4-6,7
6,7
Propane gas
3
(Hu = 25,9 kWh/m
3
)
kg/h
1,09
1,27
1,64
0,5-2,2
2,21
• Operating voltage
V/Hz
230/50
230/50
230/50
230/50
230/50
• Control voltage
V/Hz
24/50
24/50
24/50
24/50
24/50
• Min./max. wattage
Watt
29 / 60
29 / 62
29 / 66
30 / 88
30 / 102
• Standby
Watt
13
13
13
13
13
• Type of protection
IP
40
40
40
40
40
• Noise level max. (room-air dependent)
dB(A)
58
58
60
60
60
• Acoustic pressure level (dependent on assemly)
2
dB(A)
40 - 50
40 - 50
40 - 50
40 - 50
40 - 50
• Condensate quantity (natural gas) at 40 / 30°C
l/h
3,1
3,6
4,4
4,4
5,3
• Condansate pH-value
ca. 5,5
ca. 5,5
ca. 5,5
ca. 5,5
ca. 5,5
• Flue gas system: requirements, values
Temperature class
T120
T120
T120
T120
T120
Type of connection
B23, B33, C13x, C33x, C43x, C53x, C63(x), C83x
Flue gas mass flow
kg/h
49,5
57,7
74,3
81,4
100
Flue gas temperature
T
80/60°C
°C
67
69
75
75
79
Flue gas temperature
T
40/30°C
°C
45
47
52
46
49
Volume flow combustion air
Nm3/h
35,4
41,3
53,1
59,4
71,6
Delivery pressure for supply air / flue gas pipeline
Pa
90
95
115
120
140
1
The boiler series is tested for EE/H setting. Operation is possible without resetting over the Wobbe coefficient range from 12.0 to 15,0 kWh/m
3
with
a factory setting to a Wobbe coefficient of 15,7 kWh/m
3
2
Compare with protection notes .
3
TopGas
®
is also suitable für propone / butane (liquid gas)-mixtures