4 215 983 / 01
15
InSTaLLaTIOn
4.3.1 Fuel
NOTICE
The boiler is only to be operated with the fuel
stated on the boiler rating plate.
Max3 condens or Max3 condens boilers are normally
suitable for burning the following fuels:
EL lowsulphur fuel oil (sulphur content < 50 mg/kg) in
ac cordance with DIN 51 6093, or eco heating oil in ac
cor dance with SN 181160.2
All combustible gases according to DVGW Work sheet
G 260
4.3.2 Electrical connection
A qualified technician must install the electrical
supply to the equipment. The connection dia
gram is located in the electrical box of the heat
ge ne rator; the circuit diagram is supplied sep-
a rately.
Electrical connection of burner
The burner must be connected to the boiler with the
standard plug and socket connection.
The burner cable must be installed so that the plug and
socket connection has to be disconnected in order to
swing out the burner.
Max-3 condens E heating gas-side resistance
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
600
900
1200
1500
1800
2100
2400
2700
3000
3300
3600
3900
4200
4500
4800
5100
5400
5700
H
ei
zg
assei
tig
er
W
id
er
st
an
d
(m
bar
)
Kesselleistung (kW)
kW = Heizkesselleistung
Kesselvorlauftemperatur 80°C, Rücklauftemperatur 60°C
mbar = Heizgasseitiger Widerstand bei
=1.14 (Erdgas: CO
2
= 10.5%), 500 m ü.M. (Toleranz: +/- 20%)
kW = Boiler output
mbar = Flue gas resistance
=1.14 (Natural gas: CO
2
= 10.5
500 above sea level (Tolerance: +/- 20%)
(5000)
(4000)
(3000)
Heating gas-side resistance (mbar)
Boiler output (kW)
kW = Boiler output
Boiler flow temperature 80 °C, return temperature 60 °C
mbar = Heating side resistance at λ = 1.14 (natural gas H, CO
2
= 10.5 %), 500 m above sea level (tol/ 20 %)