TECHnICaL InFORMaTIOn
3.2.3 Max-3 condens E (3000-5000) for natural gas H
Type
(3000)
(4000)
(5000)
Fuel
Natural gas H
Natural gas H
Natural gas H
• Nominal heat output at 80/60 °C
kW
3162
4215
5305
• Nominal heat output at 80/30 °C
kW
3412
4546
5732
• Heat output range at 80/60 °C
kW
7743162
9824215
11955305
• Heat output range at 80/30 °C
kW
8623412
10994546
13455732
• Combustion performance
kW
7943255
10074340
12255465
• Boiler operating temperature max.
2)
°C
105
105
105
• Boiler operating temperature min.
°C
see table of operating conditions (below)
• Boiler return temperature min.
(directly in the boiler after the flue gas heat exchanger)
°C
see table of operating conditions (below)
• Safety temperature limiter setting (water side)
3)
°C
120
120
120
• Operating/test pressure
bar
6/9.6
6/9.6
10/16
• Operating/test pressure (optional)
bar
10/16
10/16
•
Boiler efficiency at 80/60 °C in full-load operation
(related to net calorific value NCV / gross calorific value GCV)
%
97.1/87.5
97.1/87.5
97.1/87.5
•
Boiler efficiency at 80/30 °C in full-load operation
(related to net calorific value NCV / gross calorific value GCV)
%
104.8/94.4
104.7/94.4
104.9/94.5
•
Boiler efficiency at 30 % partial load (EN 303)
(related to net calorific value NCV / gross calorific value GCV)
%
108.4/97.7
108.2/97.5
109.0/98.2
•
Nominal efficiency at 75/60 °C (DIN 4702-8)
(related to net calorific value NCV / gross calorific value GCV)
%
107.4/96.8
107.9/97.2
108.8/98.0
• Standby losses qB at 70°C
Watts
2166
2383
2620
• Flue gas temperature at nominal output 80/60 °C
°C
82
83
83
• Combustion gas resistance at nominal output (natural gas H, 10.5 % CO
2
),
500 m above sea level (tolerance ± 20 %)
mbar
12.2
13.4
12.0
•
Flue gas mass flow at nominal output
(natural gas H, 10.5 % CO
2
)
kg/h
4806
6408
8069
• Flow resistance boiler
1)
zvalue
0.001
0.001
0.0004
•
Flue gas heat exchanger flow resistance
zvalue
0.01
0.016
0.018
•
Boiler water flow rate at 10 K
m³/h
271
361
455
•
Boiler water flow rate at 20 K
m³/h
136
181
227
•
Minimum flue gas heat exchanger flow rate at 60 °C return flow temperature
m³/h
3.5
4.6
6.5
•
Minimum flue gas heat exchanger flow rate at 30 °C return flow temperature
m³/h
5.0
6.7
9.0
•
Boiler water capacity (incl. flue gas heat exchanger)
Litre
6525
7260
8030
•
Insulation thickness of boiler body and flue gas heat exchanger
mm
100
100
100
• Weight (incl. casing)
At operating / test pressure 6/9.6 bar
kg
7668
9265
At operating / test pressure 10/16 bar
kg
8801
10563
12905
• Combustion chamber internal dimensions
mm
900
990
1070
• Combustion chamber length (with extension into the reversing chamber,
half the length of the reversing chamber)
3436
3756
4006
• Combustion chamber volume
m³
2.186
2.891
3.602
• Dimensions
See dimensional drawing
•
Draught/underpressure at flue gas outlet max.
Pa
50
50
50
1)
Flow resistance boiler in mbar = flow rate (m
3
/h)
2
x z
2)
Limited by the boiler controller T0.2 to 105 °C.
3)
Max. safety temperature for boiler controller T0.2: 120 °C.
Operating conditions:
Fuel
EL low-sulphur fuel oil
EL eco fuel oil
Natural gas H
Boiler operating temperature min.
°C
65
75
Boiler return temperature min.
1)
°C
55
65
Return temperature control
1)
Yes
Yes
1)
Before entering boiler return