34
Chapter 6
Configuration / Setting
Subject to technical changes
Rev. 1.01.08
[P059]dO.2 - Mode of Operation of
Digital Output 2
Ø
[P058]dO.1 - Mode of Operation of Digital Output 1
Default value [CooL]
[P060]dO.3 - Mode of Operation of
Digital Output 3
Ø
[P058]dO.1 - Mode of Operation of Digital Output 1
Default value [AL1]
[P061]dO.4 - Mode of Operation of
Digital Output 4
Ó
[P058]dO.1 - Mode of Operation of Digital Output 1
(page 33)
Default value [AL2]
[P062]dIn.1 - Mode of Operation of
Digital Input 1
[P063]dIn.2 - Mode of Operation of
Digital Input 2
Ø
[P062]dIn.1 - Mode of Operation of Digital Input 1
[P064]OPt.A - Definition of
Option A
Setting of function of option A.
The factory-made default setting depends on the de--
vice specification. For controllers without options the
default setting is in each case oFF.
[P065]OPt.b - Definition of
Option B
AL4
Output switched
,
if at least one alarm defined
by
Ó
[P088]A4.d1 - Alarm Flag 4
,
Definition 1
(page 38) or
Ó
[P089]A4.d2 - Alarm Flag 4
,
Definition 2 (page 38) is active.
AL1-
Like
Ó
AL1 (page 33). Output inverted.
AL2-
Like
Ó
AL2 (page 33). Output inverted.
AL3-
Like
Ó
AL3 (page 34). Output inverted.
AL4-
Like
Ó
AL4 (page 34). Output inverted.
t1
Output switched
,
if timer 1 active
t2
Output switched
,
if timer 2 active
t3
Output switched
,
if timer 3 active
t4
Output switched
,
if timer 4 active
t1-
Output switched
,
if timer 1 is not active
t2-
Output switched
,
if timer 2 is not active
t3-
Output switched
,
if timer 3 is not active
t4-
Output switched
,
if timer 4 is not active
Co.OP Open valve
For valve control. Only degree of operation
changes are output.
Not at [P066]
,
[P067]
Co.CL
Close valve
For valve control. Only degree of operation
changes are output.
Not at [P066]
,
[P067]
Is digital input 1 active...
[oFF]
Digital input without function
P.on
... it is indicated to the controller that the pow-
er controller for heating is connected.
Is digital input 1 inactive the control is
stopped
,
no control signal and no current tol-
eran-ce alarms are generated.
P.oFF
... it is indicated to the controller that the pow-
er controller for heating is disconnected.
SP2.A
... the controller operates with the 2nd set
point.
SP3.A
... the controller operates with the 3rd set
point.
SP4.A
... the controller operates with the 4th set
point.
SP2.r
... the set point is increased or decreased by
the 2nd set point.
SP3.r
... the set point is increased or decreased by
the 3rd set point.
SP4.r
... the set point is increased or decreased by
the 4th set point.
H
.oFF
... the heating output is permanently
switched off.
H
.on
... the heating output is permanently
switched on.
C.oFF
... the cooling output is permanently
switched off.
C.on
... the cooling output is permanently
switched on.
SP.bA
SP.br
AL.CL
... the activated and stored alarm outputs are
reset.
t1
... timer 1 started by switch on edge.
t2
... timer 2 started by switch on edge.
t3
... timer 3 started by switch on edge.
t4
... timer 4 started by switch on edge.
t1-
... timer 1 started by switch off edge.
t2-
... timer 2 started by switch off edge.
t3-
... timer 3 started by switch off edge.
t4-
... timer 4 started by switch off edge.
iLoC
... entry by membrane keypad is locked. No
entry by membrane keypad is feasible.
[oFF]
Option A not available
rS
Interface RS485
dI
Digital input
dO
Digital output
AO
Analog output 0...10VDC/0...20mA
AO.O Analog output 2...10VDC/4...20mA
Is digital input 1 active...