20
Chapter 5
Display and Operation
Subject to technical changes
Rev. 1.01.08
5.3.1 Direct data entry of set point and degree of operation
In the direct data entry mode the set point and the degree of operation are directly changed by pressing the buttons
s
or
d
.
Ú
At direct data entry the data entry is accepted three seconds after the last entry.
Ú
The data entry is accepted immediately after pressing the button
f
.
Ú
Pressing the button
a
within the three seconds the data entry is canceled.
The program returns to main level and displays actual value/set point and actual value/degree of operation re-spec-
tively.
Is
Loc
displayed in the actual value display; see chapter
Ó
Display Loc (page 17).
5.3.2 Information Level
In the information level set point
,
manual mode
,
heating current and alarms are directly accessible by button
a
.
At information level
Ú
set points for temperature can be changed
,
Ú
manual mode can be switch on/off and degree of operation can be adjusted
,
Ú
an automatic current transfer can be made as well as
Ú
display of alarms and acknowledgement
.
Is
Loc
displayed in the actual value display; see chapter
Ó
Display Loc (page 17).