12 Slush ice control
0: No control
1: If evaporator thermistor reads 5°C or less,
pump motor de-energizes for 10 seconds.
2: If evaporator thermistor reads 10°C or
less, pump motor repeats de-energizing
for 10 seconds and energizing for 50
seconds. If evaporator thermistor reads
1°C, pump motor de-energizes for 10
seconds, energizes for 50 seconds, and
de-energizes for 10 seconds.
2
0
–
13
High/low
temperature
reading
High temperature harvest mode if control
board thermistor reads set point or higher
temperature. Low temperature harvest mode
if control board thermistor reads lower than
set point temperature.
60°C
5°C
1°C
14
High
temperature/
minimum harvest
time
Minimum harvest cycle time for high
temperature harvest mode.
150 sec 90 sec 5 sec
15
Low temperature/
minimum harvest
time
Minimum harvest cycle time for low
temperature harvest mode.
240 sec 120 sec 5 sec
16
Harvest
completion
temperature
Temperature to start harvest completion delay
timer. Harvest cycle ends when time is up.
12°C
6°C
0.5°C
17 Slap control 2
If bin control never trips (no ice hits detector)
during harvest cycle, another harvest cycle
begins, which repeats not more than three
times. Freeze cycle begins even if bin control
does not trip during the third harvest cycle.
ON
OFF
–
18
Harvest cycle fan
motor operation
To reduce load in harvest cycle, fan motor
energizes if control board thermistor reads
set point or higher temperature.
70°C
30°C
1°C
35
Float switch
delay timer (end
of freeze cycle)
Delay time since float switch closes at lower
float level until freeze cycle ends.
250 sec 5 sec 5 sec
42
Condenser
thermistor high
temperature
reading
Unit shuts down if condenser thermistor reads
set point or higher temperature. Automatically
reset.
90°C
40°C
2°C
43
High temperature
display
To encourage user to clean air filter, display
flashes “n92” if control board thermistor reads
set point or higher temperature. Display goes
off if thermistor reads lower than set point
temperature.
80°C
40°C
1°C
45
Fully automated
cleaning kit
detection
0: Kit not provided
1: Kit provided
1
0
–
49 Number of
chemical doses
When chemical doses reach set number of
times, notice code "n93" appears to show no
chemical is left.
15
times 3 times 1 time
56 Reset settings
Reset all user settings to default.
–
dEF
–
58 Forced shut
down
Shut down unit under any conditions. Display
shows "oFF".
–
stp
–