VII. SERVICE DIAGNOSIS
1. NO ICE PRODUCTION
PROBLEM CHECK POSSIBLE
CAUSE
REMEDY
1. OFF position.
1. Move to ON position.
2. Loose connections. 2.
Tighten.
a) Power Source
3. Bad contacts.
3. Check for continuity and
replace.
1. Loose connection. 1.
Tighten.
b) Power Cord
2. Open circuit - damaged.
2. Repair or replace.
c) Fuse
1. Blown out.
1. Replace.
1. Tripped with Bin filled
with ice.
1. Remove ice.
2. Out of position.
2. Place in position.
d) Bin Control
3. Fused contacts.
3. Check for continuity and
replace.
e) High Pressure
Control
(water-cooled,
240ME)
1. Bad contacts.
1. Check for continuity and
replace.
f) Transformer
1. Coil winding opened.
1. Replace.
g) Wiring to
Controller Board
1. Loose connections or
open.
1. Check for continuity and
repair or replace.
h) Thermistor
1. Leads short-circuit or
open and High
Temperature Safety
(Backup Timer) operates.
1. See “II. 2. [b] BEFORE
CHECKING
CONTROLLER BOARD”.
i) Hot Gas
Solenoid Valve
1. Continues to open in
freeze cycle and High
Temperature Safety
(Backup Timer) operates.
1. Check for power OFF in
freeze cycle and replace.
1. Water supply OFF and
water supply cycle does
not finish.
1. Check for recommended
pressure.
j) Water Supply
Line
(water-cooled)
2. Condenser water
pressure too low or OFF
and Pressure Control
opens and closes
frequently.
2. Check for recommended
pressure.
1. Mesh filter or orifice gets
clogged and water supply
cycle does not finish.
1. Clean.
2. Coil winding opened.
2. Replace.
k) Water Solenoid
Valve
3. Wiring to Water Valve.
3. Check for loose
connection or open, and
replace.
[1] The icemaker
will not start.
l) Controller Board
1. Defective.
1. See “II. 2. CONTROLLER
BOARD”.
1. Condenser water
temperature too warm
(water-cooled).
1. Check for recommended
temperature.
[2] Compressor
will not start, or
operates
intermittently.
a) High Pressure
Control
(water-cooled,
240ME)
2. Refrigerant overcharged.
2. Recharge.
91
Содержание IM-100
Страница 5: ...1 I SPECIFICATIONS 1 DIMENSIONS CONNECTIONS a IM 25LE Air cooled ...
Страница 6: ...2 b IM 25CLE Air cooled Until March 2000 production Auxiliary Code K 1 ...
Страница 7: ...3 c IM 21CLE IM 25CLE IM 30CLE Air cooled From April 2000 production Auxiliary Code K 2 ...
Страница 8: ...4 d IM 45LE Air cooled ...
Страница 9: ...5 e IM 45CLE 25 Air cooled ...
Страница 10: ...6 f IM 65LE Air cooled ...
Страница 11: ...7 g IM 100LE IM 130LE IM 130ME Air cooled ...
Страница 12: ...8 h IM 100CLE Air cooled ...
Страница 13: ...9 i IM 160ME Air cooled ...
Страница 14: ...10 j IM 240ME Air cooled ...
Страница 15: ...11 k IM 240M2E Air cooled ...
Страница 16: ...12 l IM 25WLE IM 30WLE Water cooled ...
Страница 17: ...13 m IM 45WLE Water cooled ...
Страница 18: ...14 n IM 65WLE Water cooled ...
Страница 19: ...15 o IM 100WLE IM 130WLE IM 130WME Water cooled ...
Страница 20: ...16 p IM 240WME Water cooled ...
Страница 21: ...17 q IM 240WM2E Water cooled ...
Страница 70: ...66 2 WIRING DIAGRAM a IM 21CLE IM 25LE IM 25CLE IM 30CLE IM 25WLE IM 30WLE ...
Страница 71: ...67 b IM 25L IM 25CL IM 25WL ...
Страница 72: ...68 c IM 45LE IM 45CLE 25 IM 45WLE ...
Страница 73: ...69 d IM 65LE IM 65WLE ...
Страница 74: ...70 e IM 65L IM 65WL ...
Страница 75: ...71 f IM 100LE IM 100CLE IM 100WLE Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 76: ...72 g IM 130LE IM 130WLE Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 77: ...73 h IM 130LE 21 IM 130WLE 21 Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 78: ...74 i IM 130ME IM 130WME Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 79: ...75 j IM 130ME 21 IM 130WME 21 Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 80: ...76 k IM 160ME ...
Страница 81: ...77 l IM 240ME IM 240WME ...
Страница 82: ...78 m IM 240M2E IM 240WM2E ...
Страница 120: ...116 Fig 30 ...
Страница 129: ...HOSHIZAKI EUROPE LTD UNIT A STAFFORD PARK 18 TELFORD SHROPSHIRE TF3 3DJ ENGLAND PHONE 01952 291777 ...