[c] EVACUATION AND RECHARGE
1) Attach Charging Hoses, a Service Manifold and a Vacuum Pump to the system. If possible,
use Quick Release Connectors onto the Access Valves (especially on the high side).
2) Turn on the Vacuum Pump.
3) Allow the Vacuum Pump to pull down to a 760 mmHg vacuum. Evacuating period depends
on the pump capacity.
4) Close the Low-side and High-side Valves on the Service Manifold.
5) Disconnect the Vacuum Pump, and attach a Refrigerant Charging Cylinder to accurately
weigh in the liquid charge. Remember to purge any air from the Charging Hose. See the
Nameplate for the required refrigerant charge.
6) Open the High-side Valve on the Gauge Manifold, and accurately measure in the liquid
charge. Close the valve on the Charging Cylinder before closing the High-side Manifold
Valve. Any remaining liquid in the line can be charged into the low side.
Note: Always charge in the liquid stage, as many refrigerants are blends and vapour
charging will affect the blend consistency (eg. R404A).
7) Turn on the icemaker. Release the High-side Access Connector, and allow pressure in
the charging line to slowly enter the low side of the system. Cap off the High-side Access
Valve. When pressure reduces on the low side, disconnect the low side charging line
and cap off the Access Valve.
8) Always cap the Access Valves to prevent a refrigerant leak.
9) Always thoroughly leak test all joints and valve caps.
10) Avoid charging large quantities of liquid into the low side in case of damage to the
Compressor.
Содержание IM-100
Страница 5: ...1 I SPECIFICATIONS 1 DIMENSIONS CONNECTIONS a IM 25LE Air cooled ...
Страница 6: ...2 b IM 25CLE Air cooled Until March 2000 production Auxiliary Code K 1 ...
Страница 7: ...3 c IM 21CLE IM 25CLE IM 30CLE Air cooled From April 2000 production Auxiliary Code K 2 ...
Страница 8: ...4 d IM 45LE Air cooled ...
Страница 9: ...5 e IM 45CLE 25 Air cooled ...
Страница 10: ...6 f IM 65LE Air cooled ...
Страница 11: ...7 g IM 100LE IM 130LE IM 130ME Air cooled ...
Страница 12: ...8 h IM 100CLE Air cooled ...
Страница 13: ...9 i IM 160ME Air cooled ...
Страница 14: ...10 j IM 240ME Air cooled ...
Страница 15: ...11 k IM 240M2E Air cooled ...
Страница 16: ...12 l IM 25WLE IM 30WLE Water cooled ...
Страница 17: ...13 m IM 45WLE Water cooled ...
Страница 18: ...14 n IM 65WLE Water cooled ...
Страница 19: ...15 o IM 100WLE IM 130WLE IM 130WME Water cooled ...
Страница 20: ...16 p IM 240WME Water cooled ...
Страница 21: ...17 q IM 240WM2E Water cooled ...
Страница 70: ...66 2 WIRING DIAGRAM a IM 21CLE IM 25LE IM 25CLE IM 30CLE IM 25WLE IM 30WLE ...
Страница 71: ...67 b IM 25L IM 25CL IM 25WL ...
Страница 72: ...68 c IM 45LE IM 45CLE 25 IM 45WLE ...
Страница 73: ...69 d IM 65LE IM 65WLE ...
Страница 74: ...70 e IM 65L IM 65WL ...
Страница 75: ...71 f IM 100LE IM 100CLE IM 100WLE Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 76: ...72 g IM 130LE IM 130WLE Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 77: ...73 h IM 130LE 21 IM 130WLE 21 Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 78: ...74 i IM 130ME IM 130WME Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 79: ...75 j IM 130ME 21 IM 130WME 21 Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 80: ...76 k IM 160ME ...
Страница 81: ...77 l IM 240ME IM 240WME ...
Страница 82: ...78 m IM 240M2E IM 240WM2E ...
Страница 120: ...116 Fig 30 ...
Страница 129: ...HOSHIZAKI EUROPE LTD UNIT A STAFFORD PARK 18 TELFORD SHROPSHIRE TF3 3DJ ENGLAND PHONE 01952 291777 ...