33
LONGER
3) Defrost Control (VR2)
The defrost control regulates the time period between
ice-drop and actuator motor restart. Any adjustment
will not be required for normal operation. Factory
setting is shown in the table below. When servicing
or replacing the controller board, adjust the Variable
Resistor VR2 using a miniature flat blade screwdriver.
Approximate Period (sec.)
IM-21CLE
IM-25LE
IM-100WLE
IM-25CLE
IM-100LE
IM-130WLE
IM-25WLE
IM-45LE
IM-130LE
IM-130WME
Ambient
IM-30CLE
IM-45CLE-25
IM-65LE
IM-130ME
IM-240ME
Temp.
IM-30WLE
IM-45WLE
IM-65WLE
IM-160ME
IM-240WME
30°C
20
20
20
20
20
20°C
30
40
40
35
30
10°C
60
80
60
90
40
4) Water Supply Control
When adjusting the Variable Resistor VR5 (Cube Control) for smaller dimple cubes, it may
be necessary to adjust the water supply time setting as well, following the instruction below.
Note: 1. See “II. 2. [a] CONTROLLER BOARD LAYOUT” for location of the Jumper Wires.
2. Any adjustment will not be required under normal use. If an insufficient water supply
results in production of cloudy ice, check to see if the Filter of the Water Valve is
clogged or water pressure is reduced.
a. IM-21CLE, IM-25LE/WLE, IM-25CLE, IM-30CLE/WLE, IM-45LE/WLE, IM-45CLE-25,
IM-65LE/WLE
Cut the jumper wire JG (marked by arrow) by
a nipper. Water supply time will be continuous
when the Water Plate is open.
Normal setting = 15 sec. with Water Plate open
Содержание IM-100
Страница 5: ...1 I SPECIFICATIONS 1 DIMENSIONS CONNECTIONS a IM 25LE Air cooled ...
Страница 6: ...2 b IM 25CLE Air cooled Until March 2000 production Auxiliary Code K 1 ...
Страница 7: ...3 c IM 21CLE IM 25CLE IM 30CLE Air cooled From April 2000 production Auxiliary Code K 2 ...
Страница 8: ...4 d IM 45LE Air cooled ...
Страница 9: ...5 e IM 45CLE 25 Air cooled ...
Страница 10: ...6 f IM 65LE Air cooled ...
Страница 11: ...7 g IM 100LE IM 130LE IM 130ME Air cooled ...
Страница 12: ...8 h IM 100CLE Air cooled ...
Страница 13: ...9 i IM 160ME Air cooled ...
Страница 14: ...10 j IM 240ME Air cooled ...
Страница 15: ...11 k IM 240M2E Air cooled ...
Страница 16: ...12 l IM 25WLE IM 30WLE Water cooled ...
Страница 17: ...13 m IM 45WLE Water cooled ...
Страница 18: ...14 n IM 65WLE Water cooled ...
Страница 19: ...15 o IM 100WLE IM 130WLE IM 130WME Water cooled ...
Страница 20: ...16 p IM 240WME Water cooled ...
Страница 21: ...17 q IM 240WM2E Water cooled ...
Страница 70: ...66 2 WIRING DIAGRAM a IM 21CLE IM 25LE IM 25CLE IM 30CLE IM 25WLE IM 30WLE ...
Страница 71: ...67 b IM 25L IM 25CL IM 25WL ...
Страница 72: ...68 c IM 45LE IM 45CLE 25 IM 45WLE ...
Страница 73: ...69 d IM 65LE IM 65WLE ...
Страница 74: ...70 e IM 65L IM 65WL ...
Страница 75: ...71 f IM 100LE IM 100CLE IM 100WLE Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 76: ...72 g IM 130LE IM 130WLE Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 77: ...73 h IM 130LE 21 IM 130WLE 21 Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 78: ...74 i IM 130ME IM 130WME Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 79: ...75 j IM 130ME 21 IM 130WME 21 Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Страница 80: ...76 k IM 160ME ...
Страница 81: ...77 l IM 240ME IM 240WME ...
Страница 82: ...78 m IM 240M2E IM 240WM2E ...
Страница 120: ...116 Fig 30 ...
Страница 129: ...HOSHIZAKI EUROPE LTD UNIT A STAFFORD PARK 18 TELFORD SHROPSHIRE TF3 3DJ ENGLAND PHONE 01952 291777 ...