[f] COMPRESSOR SOFT START
1) Startup
Power ON
3 min 20 sec
Compressor
Condenser Fan Motor
Interior Fan Motor
Cabinet Temp. Display
ON
OFF
ON
OFF
ON
OFF
When the power supply is turned on, the Temperature Display Window shows the cabinet
temperature, but the Compressor and Condenser Fan Motor start up with a 3 minute delay.
Then, the Interior Fan Motor starts up 20 seconds later.
This delay is intended to minimize the difference between the high-side and low-side
pressures and to reduce the load on the Compressor so that it can start easily in case of a
short (especially instantaneous) power failure.
2) Normal Control
2.5 min 2.5 min
Compressor
Condenser Fan Motor
Interior Thermistor
Set Point
ON
OFF
When the Compressor turns off during normal control, it has a mandatory 2.5 minute delay
before startup. For example, if the Compressor turns off by its Thermistor and the Door
is opened immediately after (causing the cabinet temperature to immediately exceed the
restart temperature), the Compressor will still not start until 2.5 minutes have passed since
its shutdown.
[g] HIGH PRESSURE SWITCH
Min 6 min
6 min
Pressure Switch
Set Point
Compressor
Condenser Fan Motor
ON
OFF
Содержание HFE-140B Series
Страница 6: ... 2 DIMENSIONS SPECIFICATIONS a HRE 70B ...
Страница 7: ... b HRE 140B ...
Страница 8: ... c HFE 70B ...
Страница 9: ... d HFE 140B ...
Страница 10: ... e HRE 70B F ...
Страница 11: ... f HRE 140B F ...
Страница 12: ... II TECHNICAL INFORMATION 1 WIRING DIAGRAM a HRE 70B ...
Страница 13: ...10 b HRE 140B ...
Страница 14: ...11 c HFE 70B ...
Страница 15: ...12 d HFE 140B ...
Страница 16: ...13 e HRE 70B F ...
Страница 17: ...14 f HRE 140B F ...
Страница 18: ...15 2 REFRIGERATION CIRCUIT Refrigerant HFC 134a HRE series HFC 404A HFE series ...