5. TIMING CHART
[a] STARTUP - CONTROL
(1) Frame Heater Control
Intermittent energization by difference between ambient and cabinet temperatures.
Energization time has 8 patterns (duty ratio 12.5% - 100%).
Duty ratio is updated every 2 min, except previous ratio is maintained during defrost
cycle.
(2) Standby at Startup
Only temperature indication is available for 3 min (not a sign of failure).
(3) Interior Fan Motor Delay at Startup
Interior Fan Motor and Frame Heater will not operate for 20 sec after Compressor
starts.
Interior Fan Motor OFF after End of Control
Interior Fan Motor will not operate for 2 min.
(4) Evaporation Signal
HRE series:
Cam Timer, for 7 min every 8 hrs
HRE-F series, HFE series: Defrost start signal, every 6 hrs
HRE, HFE series
(2)
(3)
3 min
20 sec
Power Supply
Temp Display
Frame Heater
Compressor
Condenser
Fan Motor
Interior
Fan Motor
Interior
Thermistor Temp
Set Point Temp + 1.7 K
Set Point Temp
Set Point Temp - 2.0 K
Evaporation
Signal
Evaporation Pan
Heater
Evaporation Pan
Thermostat
(1)
(4)
Содержание HFE-140B Series
Страница 6: ... 2 DIMENSIONS SPECIFICATIONS a HRE 70B ...
Страница 7: ... b HRE 140B ...
Страница 8: ... c HFE 70B ...
Страница 9: ... d HFE 140B ...
Страница 10: ... e HRE 70B F ...
Страница 11: ... f HRE 140B F ...
Страница 12: ... II TECHNICAL INFORMATION 1 WIRING DIAGRAM a HRE 70B ...
Страница 13: ...10 b HRE 140B ...
Страница 14: ...11 c HFE 70B ...
Страница 15: ...12 d HFE 140B ...
Страница 16: ...13 e HRE 70B F ...
Страница 17: ...14 f HRE 140B F ...
Страница 18: ...15 2 REFRIGERATION CIRCUIT Refrigerant HFC 134a HRE series HFC 404A HFE series ...