11.4 RS485 Termination
Proper RS485 termination minimizes signal reflections and improves reliability.
Both the MJ2 and MJ3 serial ports allow an internal termination resistor to be placed across
pins 1 and 2 by DIP Switch Setting.
Only the two devices physically located at the endpoints of the RS485 network should be
terminated.
11.5 RS485 Biasing
RS485 biasing passively asserts a line-idle state when no device is actively transmitting, which
is useful for multi-drop RS485 networking.
Both the MJ2 and MJ3 serial ports allow internal bias resistors to be switched in, pulling pin 1
up to 3.3V and pulling pin 2 down to ground. The Set Serial Ports item in the System Menu can
be used to enable RS485 biasing. Also, an application graphics screen that writes to %SR164
can do the same thing. Setting %SR164.1 enables MJ2 biasing and setting %SR164.2 enables
MJ3 biasing.
If biasing is used, it should be enabled in only one of the devices attached to the RS485
network.