MAN1032-10-EN_EXL6_UserManual
March 12, 2020
99 | 191
10.13.4 High Speed Counter Match
When either Q1 or Q2 is configured for HSC Output operation, their output state is based on a
comparison between the counter accumulator and match registers. Refer to the
10.13.5 Stepper Function
The EXL6 supports two stepper functions, one on each high-speed output when in two
counter mode. In four counter mode, the EXL6 supports one stepper function.
The Stepper requires five parameters (%AQs) to be set for operation. These parameters may
be set at run-time but ar
e ‘latched’ when the stepper
is commanded to start:
Start Frequency
(pulses per
second)
Sets the frequency for the first cycle during the acceleration phase
and the frequency of the last cycle during the deceleration phase.
When an acceleration or deceleration count is specified, the Start
Frequency must be greater than 0 and must not exceed the run
frequency or an error is generated.
Run Frequency
(pulses per
second)
Sets the frequency for the last cycle during the acceleration phase, the
consistent frequency during the run phase, and the frequency of the
first cycle during the deceleration mode. The Run Frequency must be
greater than 0 and must not exceed 5000Hz (standard), 400,000Hz
(HE-XHSQ) or 1.0 MHz (HE-XHSQ-5)
Acceleration
Count
Sets the number of cycles to occur within the acceleration phase. The
frequency of the cycles within this mode will vary linearly between the
specified Start and Run frequency. The Accel count must not equal 1 or
an error is generated. Setting this value to zero disables this phase.
Run Count
Sets the number of cycles to occur within the run phase. The frequency
of the cycles within this mode is constant at the specified Run frequency.
The Run count may be any value. Setting this value to zero disables this
phase.
Deceleration
Count
Sets the number of cycles to occur within the deceleration phase. The
frequency of the cycles within this phase will vary linearly between the
specified Run and Stop frequency. The Decel count must not equal 1 or
an error is generated. Setting this value to zero disables this phase.
Table 10.6
–
Five Parameters for Stepper Function