If communication is established, the target indicator will show the mode of the controller
Target: yy(R) as shown in the status section above in this chapter, section Cscape Status Bar.
Local ID and Target ID Match
If the controller is not communicating, ensure the target ID is set correctly. If not, set the
target ID of the controller in Cscape or on the unit. The Target ID allows directing
communications to a particular unit when multiple units are connected via a CsCAN network.
Units without CsCAN network ports respond to any network ID and do not require the ID to be
configured.
To check or change the ID on the EXL6 OCS, press the System Menu key.
The first item in the menu is Set Networks. Pressing Enter allows the ID of the unit to be
viewed or modified.
To change the Target ID of Cscape use the Controller
→
Set Target Network ID dialog.
When connected directly to the controller to which
Cscape communications are required, the Local ID
and the Target ID should match.