W8710A EQUIPMENT MONITORING SYSTEM

68-0256

8

18.

The circuit board red LED alarm light shines steadily. If it 

blinks on and off:

a. The W8710A computer and Handheld Programmer 

are communicating with each other (when keys are 

pressed or data sent back and forth).

b. It has detected a fault condition.    

19.

Start the HVAC system in the appropriate mode (cool or 

heat). Press the D/T key (upper right key on the Hand-

held Programmer) to view the temperature difference 

between the return and supply air as it rises in heat or 

falls in cool.

NOTE: If gas heat and HEAT D/T rises above 80°F (27°C), 

either increase the blower one speed higher or 

increase the CALC D/T using the Quick Heat Cali-

bration by pressing the 6 key, then the no.4 key and 

then the Up key until the desired D/T is reached.

20.

Connect a phone line from the RJ11 phone jack on the 

W8710A circuit board to any convenient phone jack.

IMPORTANT

The next step must be performed to allow the 

W8710A to dial out to the central station.

21.

Manually send your first alert report to be sure the 

W8710A is transmitting correctly (verify that the modem 

and phone line are working) and to register the W8710A 

with the Honeywell Central Station. To do this:

a. Make sure the house telephone is not in use.

b. Press the CLEAR button (a small yellow pushbutton 

above the power slide switch and white header strip 

on the circuit board) for about ten seconds until the 

red LED blinks once, shines for five seconds and 

then goes out. 

c. Listen carefully to hear the modem clicking and 

starting to dial out.

d. After one to two minutes:

(1) If the light comes back on, shining steadily, the 

report was sent successfully and your office 

should receive a manually Initiated fax report in 

approximately three minutes.

(2) If the light comes back on, blinking, the W8710A 

did not connect to the central station (busy exter-

nal phone line).Try to send the report again by 

pressing the Clear button (indicator light quits 

blinking when pressed).

(3) If the light blinks once, but does not go out, the 

house telephone is in use or the contractor code 

no. is 0, or the telephone line is faulty. To correct 

the problem, see the Troubleshooting section.

22.

Unplug the handheld programmer and fasten the cover 

on the W8710A.

Programming Your Telephone Prefix Number 

Occasionally a phone system requires a prefix number dialed 

to access an outside line. One- or two- digit prefix numbers 

can be stored in the W8710A:

1.

Plug the handheld programmer into the W8710A. 

2.

Press 9.

3.

Press 1 to change the phone prefix.

4.

Press Yes or No to change phone prefix (NN means no 

prefix numbers are required).

5.

Press 1 or 2 to select the number of digits in the prefix 

number. Press 3 if no prefix number (for example, if 

your prefix no. is 9, press 1).

6.

Enter the first digit of the prefix number and press Enter.

7.

If you pressed 2 (digits) in step 3, you will be asked to 

enter the second digit of the prefix number and then 

press Enter.

8.

Press Yes to accept the phone prefix number (the 

example shows number 9 was entered as the prefix 

number. The N after 9 indicates no 2nd digit number.)

Entering Custom Setup 

The setup values entered at the factory usually do not need 

customizing. If necessary, adjust values as follows:

1.

Press Set Up.

2.

The first screen displays the Heat D/T tolerance.

(The example shows the standard factory setting for gas heat. 

If another type of heat is programmed, the standard tolerance 

is El/- 12° or Heat Pump +/- 10°.) To change the 

tolerance, press UP or DN. When the desired tolerance 

setting is reached, press Enter.

NOTE: Tolerance is the number of degrees the operating 

temperature split (D/T) can vary (+/-) from the cali-

brated D/T before sending an alert report.

3.

The next screen displays the Cool D/T tolerance.

All standard factory settings for the Cool tolerance are       

+/-6° for all types of heating systems. To change the toler-

ance setting, press UP or DN. When the desired tolerance 

is reached, press Enter.

HEAT D/T 40
CALC D/T 55

1 – CHANGE PREFIX

2 – DIAL TONE CHK

PHONE PREFIX –NN

OKAY? YES OR NO

# PREFIX DIGITS
1,2 OR 3 = NONE

ENTER IN FIRST

DIGIT _

ENTER IN SECOND

DIGIT _

PHONE PREFIX –9N

OKAY? YES OR NO

HEAT D/T = +/- 20

UP/DN OR ENTER

COOL D/T = +/- 6

UP/DN OR ENTER

Содержание W8710A

Страница 1: ... to receive reports Operates on a small highly specialized computer that analyzes information received from its precision air measurement sensors and your system thermostat Automatically sends an alarm report when your heating and cooling system is not operating at designed specifications Automatically sends an alarm report if the temperature in your home becomes too hot or too cold Automatically ...

Страница 2: ...rgeable back up power supply provides energy to send an electrical outage report during a power outage longer than one hour Runs on 24 Vac from the heating and cooling system Accessories Required Not Included 32005322 001 Handheld Programmer Optional Not Included 32005419 001 Customer Alert Switch 32005320 001 Water Alert Float Switch 32005321 001 External Air Temperature Sensor Approvals Underwri...

Страница 3: ...mmediately receive an email with your login and password INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow these instructions can damage the product or cause a hazard ous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service ...

Страница 4: ...RTANT Install the black return air sensor where it cannot be exposed to water from a frozen evaporator coil or overflow drip Install the gray supply air sensor at least 18 in down stream from the furnace and or evaporator coil 4 Connect the 15 ft cable from the gray supply sensor to the connector marked S A on the W8710A See Fig 2 5 Connect the 7 ft cable from the black return sensor to the connec...

Страница 5: ... that can be used instead of an external air temperature sensor in mod erate climates But when maximum accuracy is desired install the 32005321 001 External Air Tem perature Sensor to override the 46 F 8 C default setting M14923 FURNACE AIR HANDLER W8710 WIRING TERMINALS THERMOSTAT F2 F2 RED YEL EXT TEMP GRN W2 G C R W Y Y O G Y W C R F1 F1 THERMOSTAT AUXILIARY SENSOR AUXILIARY SENSOR G Y W C R M1...

Страница 6: ...Code Enter any number up to eight digits to identify your customer This could be the customer s phone number or their account number 8 Fill out the Customer Web access information in the Owner s Guide now with your contractor code followed by the customer code and provide to the customer The customer can use this to view information about their system online 9 The Handheld Programmer displays the ...

Страница 7: ...g it displays Resetting Unit Please Wait 17 The Handheld Programmer displays the software ver sion again repeats the contractor number access num ber and customer number confirmation screens and ends with STATUS OK screen Table 2 Standard Calibration Settings and Setup Values System Type Standard Calibration D T Temperature Rise and Fall Standard Calibration Tolerance Range or Trip Range Low Trip ...

Страница 8: ...inks once but does not go out the house telephone is in use or the contractor code no is 0 or the telephone line is faulty To correct the problem see the Troubleshooting section 22 Unplug the handheld programmer and fasten the cover on the W8710A Programming Your Telephone Prefix Number Occasionally a phone system requires a prefix number dialed to access an outside line One or two digit prefix nu...

Страница 9: ...e such as attic or roof top unit you may need to adjust the Minimum and Maximum settings accord ingly Standard Calibration Standard calibration is the average at which most heating and cooling systems operate Standard calibration uses the calculation used to determine that the system is operating correctly See Table 2 for the W8710A standard calibration settings Customizing Standard Calibration Se...

Страница 10: ...T PRESS 2 KEY 1 Enter the system designated heat cfm 600 1000 1200 and press Enter key 2 Press Yes or No key to confirm 3 Enter Heat kW to the nearest thousand for example enter 80 rather than 79 500 and press Enter 4 Press Yes or No key to confirm 5 Turn on System Heat and press any key 6 Observe custom calibration running for System Delay Time When completed W8710A beeps and the Hand held Progra...

Страница 11: ...reading as the return air temperature NOTE After System Fan is on for five to ten minutes make sure the supply air temperature setting is identical to the return air temperature setting Calibrating Humidity Sensor NOTE Be sure sensors have enough time to stabilize ten minutes before beginning step 1 1 Press CAL 6 key on Handheld Programmer 2 Press 3 key for humidity 3 Press Yes or No key to confir...

Страница 12: ...l tone check now off 4 Observe the display screen show for ten seconds that it is resetting the unit 5 Observe the display changing to Status OK when tone checking is reinstalled Circuit Board LED Red Indicator Light The red LED has four states blinking dim illuminated and not illuminated BLINKING Blinks once When the Clear button is pressed and held for seven or more seconds the LED blinks once t...

Страница 13: ...at sys tems The calculated D T is factory set at 55 F and if necessary can be adjusted for your individual system and area See Customizing Standard Calibration Set tings section 4 The factory set tolerance range in a gas heating appli cation is 20 F calculated D T This example has a tolerance range of 35 F to 75 F If desired the toler ance range can be increased or decreased for individ ual system...

Страница 14: ...oling temperature increases For example at 50 percent rela tive humidity the computer calculates that the system temperature difference is 18 F If the relative humidity is lower than 50 percent the temperature difference is greater than 18 F Supply Air Temperature 20 Tolerance Range Calculated 55 Temperature Rise Return Air Temperature 20 Tolerance Range Above 75 High D T Alert Report 75 Gas Heat ...

Страница 15: ...n 24 F a High D T Alert Report is generated 12 When the temperature fall between the return and sup ply sensors is measured and is lower than 12 F a Low D T Alert Report is generated Supply Air Temperature Return Air Temperature 0 50 Relative Humidity 100 Calculated Temperature Fall Changes with Relative Humidity Cooling Supply Air Temperature Return Air Temperature 0 50 Relative Humidity 100 18 C...

Страница 16: ...y Initiated or Monthly Check in 5 Activation or renewed date If operated less than one year this is the activation installation date of the W8710A After one year it is the most recent anniver sary renewed date 6 Readings at the time this report was faxed were The sensor data and monitor calculation at the time the alert report was transmitted to the Honeywell Central Station M14925A HONEYWELL ALER...

Страница 17: ...re Sensor is connected The External Air Temperature Sensor is required on heat pump systems but can also be used with conventional systems when outside temperature is desired 12 Hour of operation Shows the hours of operation for each mode cooling heating and fan This information is used for scheduling routine maintenance service and air filter cleaning 13 Mode setting Shows the unit operating mode...

Страница 18: ... and test for dial tone with a portable telephone Check telephone line for bad connections or cable Reattempt to manually initiate call by pressing the Clear button Press ID key and re enter numbers if incorrect Press the TEL 9 key and enter the required prefix numbers Check with the office to confirm it is working correctly If OK confirm that the Honeywell Central Station has the correct fax numb...

Страница 19: ...cation Error Loc 1 Handheld Programmer was plugged into circuit board before monitor was turned on Handheld Programmer was plugged in when power slide switch was turned off and then on Return air sensor was unplugged and then connected to the circuit board 24V not available to the unit and battery is low Loose damaged or Handheld Programmer cable RJ45 connector ends Unplug Handheld Programmer turn...

Страница 20: ...ome RPH DQG XLOGLQJ RQWURO RPH DQG XLOGLQJ RQWURO RQH ZHOO RQH ZHOO LPLWHG RQH ZHOO LPLWpH RXJODV ULYH 1RUWK QDPLF ULYH ROGHQ 9DOOH 01 6FDUERURXJK 2QWDULR 0 9 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Отзывы: