2.8.11
Keyboard
When running Dell diagnostics the USB keyboard must be connected to a USB port on the back panel.
After connecting the keyboard, you must download the latest diagnostics from the Dell Support Website
at
.
Honeywell offers a cabinet mounted 8-port KVM switch/control console (model number TP-KVMCB1 for
switch with PS/2 interface and model number TP-KVMCB2 for switch with USB interface) to a provide
human interface (booting and maintenance activities) to cabinet mounted servers. Either option comes
pre-installed from the Honeywell factory.
2.8.12
Video cable
The video cable must support DDC. If either a monitor or video cable that does not support DDC is
connected, the display generator defaults to a resolution that precludes communication with the system
software and stops startup. A quick check to determine if a cable is DDC compatible is to check if the
pins 5, 9, and 12 of the HD 15 connector are wired. The supplied cable, part number 51196742-200 is
DDC compatible.
The server platform supports industrial standard video formats, typically 1280X1024, at a refresh rate of
75Hz or 1024X768 at a refresh rate of 75Hz.
2.9
Industrial regulatory compliance
The compliance specifications in this section apply to cabinet installations.
WARNING
Honeywell does not claim Safety Compliance or Electromagnetic Compatibility (EMC)
Compliance for system equipment configurations that have not been described in this guide as
standard system configurations. Any equipment configuration other than that described in this
publication decertifies the Safety and EMC compliance of this product.
l
l
2.9.1
Electromagnetic Compatibility
The following table provides the Electromagnetic Compatibility (EMC) specifications (Industrial
Regulatory) for European community.
Element
Description
Emissions
EN 61326-1:2006 (Industrial Locations, CISPR 11, Class A)
Immunity
EN 61326-1:2006 (Industrial Locations)