6
OPERATION
62
SMARTLINE® RM60 (FMCW)
www.honeywell.com/ps
34-VF-25-31 iss.4 GLO December 15 US
Data dependencies for the 4 mA settings of outputs 1 and 2
C.5.1.5
Volume Unit
The volume unit displayed in operator
mode.
m3, L, US gal, GB gal, ft3, bbl
m3
C.5.1.6
Mass Unit
The mass unit displayed in operator
mode.
Tons, Kg, US Tons, GB Tons
Kg
C.5.1.7
Custom.
Length Unit
A non-standard length unit for the
conversion table. This is defined by the
supervisor.
LEN_FREE_
C.5.1.8
Custom.
Length Ratio
The conversion factor between the
length unit selected in C.5.1.4 (Length
Unit) and C.5.1.7 (Custom. Length
Unit). This ratio is a multiple of 1 mm.
min.-max: 1
…
99999
1
C.5.1.9
Custom. Conv.
Unit
A non-standard conversion unit for the
conversion table. This is defined by the
supervisor.
CO_FR_UN
C.5.2
C.5.2
C.5.2
C.5.2
Passwords
Passwords
Passwords
Passwords
To change user passwords, refer to
To change user passwords, refer to
To change user passwords, refer to
To change user passwords, refer to
these menu items.
these menu items.
these menu items.
these menu items.
C5.2.2
Supervisor
This changes the supervisor password.
Push the keypad buttons up to 6 times
in any order. This will be the new
password. To confirm the change,
enter the new password a second time.
[>>>>], [
^
^
^
^
], [
],
[
], [>
>>>], [
^
^
^
^
]
C.6 Reset
C.6.2
Clear Error
Record
Erase the error record in menu item
B.2.6. Push [
^
^
^
^
] to confirm.
C.6.3
Restart
If the device is not functioning properly,
this menu item will restart the device.
Push [
^
^
^
^
] to confirm.
1
Units and range depend on the output function, length unit and volume unit selected. See also the table of data dependencies for the
4 mA settings in this section.
2
Units and range depend on the output function, length unit and volume unit selected. See also the table of data dependencies for the
20 mA settings in this section.
3
This function is applicable only to a device that has two outputs
Output function
Minimum value
Maximum value
Default
Level
0 m
<20 mA Setting for Level
0 m
Volume
0.00 m
³
<20 mA Setting for Volume
0 m
³
Mass
0.00 kg
<20 mA Setting for Mass
0 kg
Distance
0 m
<20 mA Setting for Distance
0 m
Ullage Volume
0.00 m
³
<20 mA Setting for Ullage Volume
0 m
³
Ullage Mass
0.00 kg
<20 mA Setting for Ullage Mass
0 kg
Menu
No.
Function
Function description
Selection list
Default
Содержание SmartLine RM60
Страница 4: ...4 www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ABOUT THIS DOCUMENT SMARTLINE RM60 FMCW ...
Страница 8: ...CONTENTS 8 www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US SMARTLINE RM60 FMCW ...
Страница 16: ...1 SAFETY INSTRUCTIONS 16 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 34: ...3 INSTALLATION 34 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 40: ...4 ELECTRICAL CONNECTIONS 40 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 76: ...6 OPERATION 76 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 86: ...7 SERVICE 86 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 104: ...8 TECHNICAL DATA 104 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 114: ...9 DESCRIPTION OF HART INTERFACE 114 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 126: ...10 APPENDIX 126 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 127: ...APPENDIX 10 127 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...