Tracing
Velocity
This function sets the maximum rate of
change of level. The measured value
cannot change faster than the tracing
velocity.
min-max:
0.001
…
10.000 m/min /
0.003
…
32.8 ft/min
0.5 m/min /
1.64 ft/min
C.1.16
Multiple
Reflections
Multiple reflections will cause the
device to display smaller readings.
Objects in the silo, sharp corners,
installation of the device on a large
nozzle or at the centre of a dome roof
can cause multiple reflections. A very
calm surface or a silo with a small
convex or flat roof can also cause
multiple reflections.
Yes, No
No
C.1.17
Empty Spect.
OnOff
This function starts and stops
interference signal filter. Interference
signals are the result of fixed and
moving obstacles inside the silo. If you
must do a spectrum analysis, record
an empty spectrum first. Go to the
"Empty Spectrum" menu (A.1.3.0) in
the Quick Setup list.
On, Off
Off
C.1.19
Units For
Tables
Sub-menu for volume and mass
conversion operations.
C.1.19.1
Table Length
Unit
The length unit used in the conversion
table. If "Free Unit" is selected, the
device uses the unit name in menu
item C.5.1.7.
m, cm, mm, inch, ft, Free Unit
m
C.1.19.2
Conversion
Unit
The volume or mass unit used in the
conversion table. If "Free Unit" is
selected, the device uses the unit name
in menu item C.5.1.9.
m3, L, US gal, GB gal, ft3, bbl,
Tons, Kg, US Tons, GB Tons,
Free Unit
m3
C.1.20
Product
Density
A value greater than 0 that is used with
a volume conversion table to start the
mass calculation. This menu item is
not available if you have selected a
mass unit.
0
…
20000 kg/m3
0
C.1.21
Volume / Mass
Table
The device uses this table to display
volume and mass readings. Give the
number of entries on the table. Push
[
^
^
^
^
]. Type in the level and
corresponding volume / mass values.
Number of entries min.-max:
0
…
50
No table. Table
units are
selected in
menu items
C.1.19.1 and
C.1.19.2.
C.1.22
Linearisation
Table
The device uses this table to increase
on-site accuracy. Give the number of
entries plotted. Fill the silo. Make a
reference measurement and type in
the correct value next to the device
reading. For more data, refer to
Linearisation
on page 64.
Number of entries min.-max:
0
…
50
0
C.3 Output 1 (HART)
C.3.1
Output
Function
Select an output function to scale the
current values. This is not displayed in
the operator mode.
Level, Distance, Volume
(Mass), Ullage Volume (Ullage
Mass), Reflection
Level
C.3.2
4 mA Setting
Give a measurement value to 4 mA.
min.-max:
1
0 m / 0 ft
C.3.3
20 mA Setting
Give a measurement value to 20 mA.
min.-max:
2
Depends on the
output function
C.3.4
Output Range
Sets the effective range of output 1
either with or without over-run.
min.-max: 3.8
…
20.5 mA
(NAMUR), 4
…
20 mA
4
…
20 mA
Menu
No.
Function
Function description
Selection list
Default
Содержание SmartLine RM60
Страница 4: ...4 www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ABOUT THIS DOCUMENT SMARTLINE RM60 FMCW ...
Страница 8: ...CONTENTS 8 www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US SMARTLINE RM60 FMCW ...
Страница 16: ...1 SAFETY INSTRUCTIONS 16 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 34: ...3 INSTALLATION 34 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 40: ...4 ELECTRICAL CONNECTIONS 40 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 76: ...6 OPERATION 76 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 86: ...7 SERVICE 86 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 104: ...8 TECHNICAL DATA 104 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 114: ...9 DESCRIPTION OF HART INTERFACE 114 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 126: ...10 APPENDIX 126 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Страница 127: ...APPENDIX 10 127 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...