Operation
SDC / DHC 43
37
EN2H-0220 GE51 R1005
►
Alternatively, the value can be acquired by automatic
exit after approx. 60 s.
Factory setting
16
°C
Setting range
5...30
°C
4.2.3.3.3 Separate Operating Mode
Function
In control mode 2 the selected program applies only for
the heating circuit specified previously.
Hence, each heating circuit can be assigned its own
operating mode.
Setting:
►
Press the "operating mode" key
¢
.
►
Select the desired heating circuit, i.e. HC, MC-1 or
MC-2, with the rotary pushbutton
î..
►
Confirm the circuit by pressing the pushbutton
î..
►
Set the flashing operating mode by turning to the
desired value.
►
Confirm the set value by pressing the "operating
mode"
¢
or the rotary pushbutton
î
.
►
In case of short-term operating modes (Holiday,
Absence, Party) set the desired target value by
turning the rotary pushbutton
î
and confirm the set
value as described above.
►
Alternatively, the value can be acquired by automatic
exit after the set INFO-TIME (see "System
Information).
4.2.3.4 Summer Switch-off (heating limit)
Function
This parameter determines the end of the heating
season based on the outside temperature according to
the following criteria:
Rapid increase of the outside temperature
As long as the mean outside temperature is below the
OP. MODE
MC 2
æ ç è é ê ë ì í
AUTOMATIC
MC 2
æ ç è é ê ë ì í