Operation
SDC / DHC 43
39
EN2H-0220 GE51 R1005
Settings:
►
With the flashing reset display
PARAM.-RESET
press the rotary pushbutton.
►
The flashing reset ready indication (
SET
)
appears.
►
Press the rotary pushbutton for approx. 5 s.
In case of a reset, the confirmation
RESET OK
appears
briefly, then -in order of feedback- the first parameter in
the relevant menu is called.
4.2.4 Domestic Hot Water Menu
This menu comprises all the parameters necessary for
the programming of the DHW circuit with the exception of
the DHW time program.
NOTE
This menu can be called only if the heating technician
has activated a DHW loading pump or a DHW circulation
pump.
4.2.4.1 DHW Economy Temperature
Function
This parameter determines the temperature in the
domestic hot water heater between the heating cycles in
automatic mode.
Factory setting
40
°C
Setting range
10 °C...DHW normal temperature setting
NOTE
If a DHW thermostat is used to determine the water
heater temperature, this parameter is skipped.
4.2.4.2 Legionella Protection-Day
Factory setting
OFF
Setting range
OFF, MON. to SUN., ALL