Operation
SDC / DHC 43
19
EN2H-0220 GE51 R1005
Display
An active standby mode appears on the basic display
with the indication
STANDBY
.
4.1.2.6 "Heating Characteristic" Key
This key makes it possible to set the heating
characteristics for the system’s heating circuits.
The slope of the heating characteristic describes the
relation between the change in the flow temperature with
the change in the outside temperature. In case of large
heating surfaces like floor heating systems the heating
characteristic is less steep compared to smaller heating
surfaces (e.g. radiators).
The set value refers to the lowest outside temperature at
the basis of the heat demand calculation.
IMPORTANT NOTE!
This parameter is to be set by the heating technician and
should not be altered anymore.
Setting:
►
Press "heating characteristic" key
£
.
►
Turn the rotary pushbutton
î
in order to select the
desired heat circuit.
►
Confirm the set value by pushing the rotary
pushbutton
î
.
►
Turn the rotary pushbutton
î
in order to set the
characteristic type.
►
Confirm the set value by pushing the rotary
pushbutton
î
.
►
Adjust the flashing value and confirm.
►
To return to the basic display, press the "heating
characteristic" key
£
.
►
Alternatively the value can be acquired by automatic
exit after the set INFO-TIME (see "System
Information).
Setting Range
0.20...3.5
Factory Setting
Direct heating circuit
(DK):
= 1.50
Mixer heating circuit 1
(MK1): = 1.00
Mixer heating circuit 2
(MK2): = 1.00
HEATCURVE
MC1
1.20
æ ç è é ê ë ì í
£