SDC / DHC 43
Operation
EN2H-0220 GE51 R1005
22
Set Time for
If the "information key"
¤
is pressed for approx. 3 s
Automatic
Exit
upon accessing the information
level, the INFO-TIME parameter appears.
This parameter determines the time for the automatic
return to the basic display.
Setting range
OFF, 1...60 min
OFF
No exit, the last information displayed
remains constantly until the next setting on
the display.
1...60 min
Automatic exit from the information level
after the specified time, settable in 0.5
minute steps.
Factory setting
OFF
4.1.2.8 "Manual Mode" / "Emission Measurement" Key
4.1.2.8.1 "Manual
Mode"
If the "manual mode" / "emission measurement" key is
pressed for more than 5 s while the basic display is
visualized, the controller is switched to manual mode. In
this operating mode the heat generator temperature is
set manually with the rotary pushbutton
î
according to
the desired setpoint. All the pumps are active, while the
available mixing valves are de-energized and can be
actuated by hand.
The heat generator setpoint can be set from 5 to 90 °C
and it flashes on the left hand of the display, while the
actual heat generator temperature is visualized statically
on the right hand of the display.
MANUALMODE
38.0
o
C
40.0
o
c
æ ç è é ê ë ì í
INFO-TIME
2.0
min
æ ç è é ê ë ì í