53
65-0120—1
RM7838B
TROUBLESHOOTING
TABLE 14—EXPANDED ANNUNCIATOR FAULT CODES (Continued)
Annunciation Message
Symbol
System Faults
LOCKOUT nnh
*High Oil Pres.*
EA
Oil pressure was above high oil pressure limit.
LOCKOUT nni
*Low Oil Pres.*
EA
Oil pressure was below low oil pressure limit.
LOCKOUT nnj
*High Oil Temp.*
EA
Oil temperature was above high oil temperature limit.
LOCKOUT nnk
*Low Oil Temp.*
EA
Oil temperature was below low oil temperature limit.
LOCKOUT nnm
*Atomizing Sw.*
EA
Atomizing switch failed to close.
LOCKOUT nnn
*High Gas Pres.*
EA
Gas pressure was above high gas pressure limit.
LOCKOUT nno
*Low Gas Pres.*
EA
Gas pressure was below low gas pressure limit.
LOCKOUT nnp
*Airflow Switch*
EA
The Airflow Switch was open when it should have been closed
or vice versa.
LOCKOUT nnq
*Aux. ILK #4*
EA
Auxiliary Interlock #3 was open.
LOCKOUT nnr
*Aux. ILK #5*
EA
Auxiliary Interlock #4 was open.
LOCKOUT nns
*Other ILKs*
EA
Other Auxiliary Interlocks were open.
LOCKOUT nny
*Valve Closure*
EA
Preignition Interlock or other valve closure switch was open.
LOCKOUT nnz
*Other PIIs*
EA
Other Preignition Interlocks were open.
EXPANDED ANNUNCIATOR DIAGNOSTIC
CURRENT STATUS MESSAGES (TABLE 15)
These message are used to provide information from the
Expanded Annunciator to the Keyboard Display Module in
Current Status EA Diagnostics, see Table 5. This informa-
tion explains the first limit or interlock that is de-energized in
the system.
TABLE 15—EXPANDED ANNUNCIATOR
DIAGNOSTIC CURRENT STATUS MESSAGES.
Display
Description
Burner Sw.
Burner Switch
Oper. Control
Operating Control
Aux. Limit #1
Auxiliary Limit #1
Aux. Limit #2
Auxiliary Limit #2
LWCO
Low Water Cutoff
High Limit
High Temperature or
High Pressure Limit
Aux. Limit #3
Auxiliary Limit #3
FuelSelectOff
Fuel Select Off
BothFuelSelect
Both Fuels Selected
High Oil Pres.
High Oil Pressure
Low Oil Pres.
Low Oil Pressure
High Oil Temp.
High Oil Temperature
Low Oil Temp.
Low Oil Temperature
Atomizing Sw.
Atomizing Switch
High Gas Pres.
High Gas Pressure
Low Gas Pres.
Low Gas Pressure
Airflow Sw.
Airflow Switch
Aux. ILK #4
Auxiliary Interlock #4
Aux. ILK #5
Auxiliary Interlock #5
All switches on