TABLE 13—EXPANDED ANNUNCIATOR HOLD CODES.
Annunciation Message
Symbol
System Holds
BURNER OFF: T6
(Burner Switch)
EA
Burner switch is open.
STANDBY HOLD: T6
(Aux. Limit #1)
EA
Auxiliary limit #1 is open.
STANDBY HOLD: T6
(Aux. Limit #2)
EA
Auxiliary limit #2 is open.
STANDBY HOLD: T6
(LWCO)
EA
Open low water cutoff.
STANDBY HOLD: T6
(High Limit)
EA
High limit (pressure or temperature) exceeded.
STANDBY HOLD: T6
(Aux. Limit #3)
EA
Auxiliary limit #3 is open.
STANDBY HOLD: T6
(FuelSelect Off)
EA
No fuel selected.
STANDBY HOLD: T6
(BothFuelSelect)
EA
Both fuels selected.
STANDBY HOLD: T6
(High Oil Pres.)
EA
Oil pressure is above high oil pressure limit.
STANDBY HOLD: T6
(Low Oil Pres.)
EA
Oil pressure is below low oil pressure limit.
STANDBY HOLD: T6
(High Oil Temp.)
EA
Oil temperature is above high oil temperature limit.
STANDBY HOLD: T6
(Low Oil Temp.)
EA
Oil temperature is below low oil temperature limit.
STANDBY HOLD: T6
(Atomizing Sw.)
EA
Atomizing Switch is open.
STANDBY HOLD: T6
(High Gas Pres.)
EA
Gas pressure is above high gas pressure limit.
STANDBY HOLD: T6
(Low Gas Pres.)
EA
Gas pressure is below low gas pressure limit.
STANDBY HOLD: T6
(Circuit Fault)
EA
Control input is not energized.
TABLE 14—EXPANDED ANNUNCIATOR FAULT CODES.
Annunciation Message
Symbol
System Faults
LOCKOUT nna
*Aux. Limit #1*
EA
Auxiliary limit #1 was open.
LOCKOUT nnb
*Aux. Limit #2*
EA
Auxiliary limit #2 was open.
LOCKOUT nnc
*LWCO*
EA
Open low water cutoff.
LOCKOUT nnd
*High Limit*
EA
High limit (pressure or temperature) was exceeded.
LOCKOUT nne
*Aux. Limit #3*
EA
Auxiliary limit #3 was open.
LOCKOUT nnf
*FuelSelect Off*
EA
No fuel selected.
LOCKOUT nng
*BothFuelSelect*
EA
Both fuels selected.
(continued)
RM7838B
TROUBLESHOOTING