SPECIFICATIONS
TABLE 1—TERMINAL RATINGS (Continued).
Terminal No.
Description
Ratings
F(11)
Flame Sensor
60 to 220 Vac, current limited.
12
Firing Rate High Fire
120 Vac, 75 VA pilot duty.
13
Firing Rate Common
120 Vac, 75 VA pilot duty.
14
Firing Rate Low Fire
120 Vac, 75 VA pilot duty.
15
Firing Rate Modulate
120 Vac, 75 VA pilot duty.
16
Pilot Valve Hold Input
120 Vac, 1 mA.
17
Manual Open Switch
120 Vac, 1 mA.
18
Low Fire Switch
120 Vac, 1 mA.
19
High Fire Switch
120 Vac, 1 mA.
20
Preignition Interlock
120 Vac, 1 mA.
21
Start Switch Input
120 Vac, 1A pilot duty.
22
Shutter
120 Vac, 0.5 A.
1
The RM7838B must have an earth ground providing a connection between the subbase and the control panel or the boiler. The
earth ground wire must be capable of conducting the current to blow the 20A fuse (or breaker) in event of an internal short
circuit. The RM7838B needs a low impedance ground connection to the equipment frame which, in turn needs a low
impedance connection to earth ground. For a ground path to be low impedance at RF frequencies, the connection must be
made by minimum length conductors having maximum surface areas. Wide straps or brackets are preferred rather than
leadwires. Be careful to ensure that mechanically tightened joints along the ground path, such as pipe or conduit threads or
surfaces held together with fasteners, are free of nonconductive coatings and are protected against mating surface corrosion.
2
2000 VA maximum connected load to RM7838B Assembly.
3
Can also be 120 Vac, 1A pilot duty.
4
Can also be 65 VA pilot duty with motorized valve, 1150 VA inrush, 460 VA open, 250 VA hold.
5
Operating frequency chosen by RM7838B selection.
TABLE 2—FLAME DETECTION SYSTEMS (FIGS. 4, 5, 6).
(Continued)
Plug-in Flame Signal Amplifiers
Applicable Flame Detectors
Type
Color
Self-
Checking
Model
Flame
Failure
Response
Time
Fuel
Type
Models
Rectification Green
No
R7847A
.8 or 3 sec
Gas
Rectifying
Flame Rod
Holders
a
C7004, C7007, C7011.
CompleteAssemblies:
C7008, C7009, Q179.
No
R7847A
.8 or 3 sec
Oil
Rectifying
Photocell
C7003, C7010, C7013,
C7014.
b
No
R7847A
3 sec
Gas, oil,
coal
Ultraviolet
(PurplePeeper)
C7012A,C.
c
Dynamic
AMPLI-
CHECK™
R7847B
d
.8 or 3 sec
Gas
Rectifying
Flame Rod
Holders
d
C7004, C7007, C7011.
Complete Assemblies:
C7008, C7009, Q179.
Dynamic
AMPLI-
CHECK™
R7847B
d
.8 or 3 sec
Oil
Rectifying
Photocell
C7003, C7010, C7013,
C7014.
b
Dynamic
AMPLI-
CHECK™
R7847B
d
3 sec
Gas, oil,
coal
Ultraviolet
(Purple Peeper)
C7012A,C.
c
Содержание RM7838B Series