65-0120—1
26
RM7838B
OPERATION
INITIATE
POWER
PILOT
FLAME
MAIN
ALARM
ALARM
STANDBY
(INDEFINITE)
POWER
ALARM
POWER
DRIVE
TO
H. F.
DRIVE
TO
L. F.
DRIVE
TO
L. F.
MAIN
VALVE
PFEP
HOLD
5
SECONDS
MAX.
10 SEC.
10 SEC.
10 SEC.
10 SEC.
45 SEC.
HOLD
(INDE-
FINITE)
HOLD
(INDEFINITE)
PURGE
PREPURGE TIME IS
SELECTABLE THROUGH
VARIOUS ST7800
PURGE TIMER CARDS
PFEP
J1 INTACT-10 SEC.
J1 CLIPPED-4 SEC.
MFEP
MFEP
NORMAL
BURNER
RUN
NORMAL
BURNER
RUN
RM7838B ENERGIZED (TERMINAL 4 AND L2)
TERMINAL 3 ENERGIZED (ALARM)
TERMINAL 6 ENERGIZED (START/STOP SWITCH)
L. F. SWITCH CLOSED (TERMINAL 18)
H F. SWITCH CLOSED (TERM. 19)
PREIGNITION INTERLOCKS CLOSED (TERM. 20 ENERGIZED)
SAFE START CHECK
TERMINAL 13 TO 12
TERMINAL
13 TO 15
TERMINAL
13 TO 15
TERMINAL 13 TO 14
TERMINAL 13 TO 14
TERMINAL 13 TO 14
TERMINAL 18
TERM. 10
TERM. 10
TERM. 21 ENERGIZED
TERMINAL 5 ENERGIZED (COMBUSTION AIR FAN)
TERMINAL 7 ENERGIZED (COMBUSTION AIRFLOW SWITCH)
TERMINAL 8 ENERGIZED (J2 INTACT)
TERMINAL 17 ENERGIZED
TERMINAL 16 ENERGIZED
FLAME PROVING
TERMINAL 9
TERMINAL 8 ENERGIZED (J2 CUT)
TERMINAL 8
MAIN
PILOT
FLAME
POWER
MAIN
PILOT
FLAME
POWER
MAIN
PILOT
FLAME
POWER
MAIN
PILOT
FLAME
POWER
MAIN
PILOT
FLAME
POWER
MAIN
PILOT
FLAME
POWER
MAIN
PILOT
FLAME
POWER
MAIN
PILOT
FLAME
POWER
MAIN
PILOT
FLAME
POWER
M9744
PILOT VALVE HOLD
2
4
1
2
WHEN CONFIGURATION JUMPER J3 IS CLIPPED, THE RM7838B AUTOMATICALLY
CONTINUES INTO THE MFEP (NO WAITING TIME BETWEEN THE PFEP AND MFEP).
ALARM (TERMINAL 3) IS DEENERGIZED AS SOON AS FLAME IS DETECTED.
3
4
NORMAL SHUTDOWN OCCURS WHEN TERMINAL 6 IS DEENERGIZED.
THE RM7838B STARTS THE
PILOT VALVE HOLD
SEQUENCE WHEN TERMINAL 16 IS ENERGIZED.
THE RM7838B REMAINS IN
PILOT VALVE HOLD
INDEFINITELY OR UNTIL TERMINAL 16 IS DE-ENERGIZED.
3
1
PFEP
INITIATE
PURGE
MFEP
RUN
MFEP
RUN
PILOT
VALVE
HOLD
(CLOSED)
PILOT
VALVE
HOLD
(CLOSED)
PILOT
VALVE
HOLD
(CLOSED)
PILOT
VALVE
HOLD
(CLOSED)
M. O. V. SWITCH
CLOSED
LED
DISPLAY
20
10
00
00
00
00
00
45
55
10
J3 INTACT
BURNER
OPERATING
CONTROLS
AND
INTERLOCKS
FLAME
SIGNAL
FIRING
RATE
M OTOR
Fig. 22—Operation of the RM7838B Relay Module (operation including pilot valve hold).
Содержание RM7838B Series