65-0120—1
32
TABLE 5—EXPANDED ANNUNCIATOR.
Selectable Message
Display Value
First Line
(Second Line)
(Second Line)
Message
◊
Expanded Annun.
1
↔
◊
Expanded Annunciator (EA not connected)<
◊
Current Status (CS:)
±
EA Message<
↓
EA
◊
Valve Closure (Valve Close)
T4
ON or OFF<
↓
EA
◊
Burner Switch (Burner Sw)
T5
ON or OFF<
↓
EA
◊
Operating Control (OperControl)
T6
ON or OFF<
↓
EA
◊
Auxiliary Limit (Aux Limit 1)
T7
ON or OFF<
↓
EA
◊
Auxiliary Limit (Aux Limit 2)
T8
ON or OFF<
↓
EA
◊
Low Water Cutoff (LWCO)
T9
ON or OFF<
↓
EA
◊
High Limit (High Limit)
T10
ON or OFF<
↓
EA
◊
Auxiliary Limit (AuxLimit 3)
T11
ON or OFF<
↓
EA
◊
Oil Selection Switch (Oil Select)
T12
ON or OFF<
↓
EA
◊
High Oil Pressure Switch (Hi OilPres)
T13
ON or OFF<
↓
EA
◊
Low Oil Pressure Switch (LowOilPres)
T14
ON or OFF<
↓
EA
◊
High Oil Temperature Switch (Hi OilTemp)
T15
ON or OFF<
↓
EA
◊
Low Oil Temperature Switch (LowOilTemp)
T16
ON or OFF<
↓
EA
◊
Atomizing Switch (Atomize Sw)
T19
ON or OFF<
↓
EA
◊
Gas Selection Switch (Gas Select)
T17
ON or OFF<
↓
EA
◊
High Gas Pressure Switch (Hi GasPres)
T18
ON or OFF<
↓
EA
◊
Low Gas Pressure Switch (LowGasPres)
T19
ON or OFF<
↓
EA
◊
Airflow Switch (Airflow Sw)
T20
ON or OFF<
↓
EA
◊
Auxiliary Interlock (Aux ILK 4)
T21
ON or OFF<
↓
EA
◊
Auxiliary Interlock (Aux ILK 5)
T22
ON or OFF<
↓
EA
◊
EA Fault Code
nnn<
↓
EA
◊
Software Revision (SW Rev.)
nnnn<
↓
EA
1
Expanded Annunciator Diagnostic Current Status Messages can be reviewed in Table 15.
RUN/TEST SWITCH FUNCTIONS
The Run/Test switch is located on the top side of the
RM7838B, see Fig. 27. The Run/Test Switch allows the
burner sequence to be altered as follows:
1. In Purge Drive To High Fire Position, the Run/Test
switch, when placed in the TEST position, will hold in
PURGE with the firing rate motor in the High Fire position.
2. During the time measured PURGE sequence, the Run/
Test switch, when placed in the TEST position, will cause the
PURGE timing to stop. The firing rate motor will be in the
High Fire position.
3. In Purge Drive to Low Fire position, the Run/Test
switch, when placed in the TEST position, will hold the
burner sequence in PURGE with the firing rate motor in the
Low Fire position.
4. In PFEP, the Run/Test switch, when placed in the
TEST position, will stop the timer during the first eight
seconds when a ten second PFEP is selected or during the
first three seconds when a four second PFEP is selected,
allowing pilot-turn-down test and other burner adjustments
to be made. This activates a 15 second flameout timer that
permits pilot flame adjustment without nuisance safety shut-
downs. The Run/Test Switch will be ignored during PFEP
for the RM7838B if terminals 8 and 9 are jumpered.
5. During Run, the Run/Test Switch, when placed in the
TEST position, will drive the firing rate motor to the Low
Fire position.
NOTE: When the RM7838B is switched to the TEST
mode, it will stop and hold at the next Run/Test switch
point in the operating sequence. Make sure that the Run/
Test Switch is in the RUN position before leaving the
installation.
SELECTABLE SITE-CONFIGURABLE JUMPERS
The RM7838B has three site-configurable jumper op-
tions, see Fig. 28 and Table 6. The site-configurable jumpers
should be clipped with side cutters and the resistors removed
from the Relay Module.
RM7838B
OPERATION