51
65-0120—1
TABLE 12—HOLD AND FAULT MESSAGE SUMMARY (Continued)
Annunciation Message
System Failure
Fault 49
*Man-Open Sw. On*
MOS was on when it should be off.
Fault 50
*Jumpers Wrong*
Incorrect combination of configurable jumpers was selected.
Fault 51
*Flame Too Strong*
Flame signal value is too high.
Fault 52 - 70
*Call Service*
Internal fault codes. Unused.
Fault 71 - 75
*Device Specific*
Internal fault codes. Unused.
Fault 76 - 93
*Accessory Fault*
Internal fault codes. Unused.
Fault 94 - 104
*Call Service*
Internal fault codes. Unused.
Fault 105
*Call Service*
Internal Fault. Relay Module self-test failure.
Fault 106
*Call Service*
Internal Fault. Relay Module self-test failure.
Fault 107
*Call Service*
Internal Fault. Relay Module flame signal crosscheck failure.
Fault 108
*Call Service*
Unused.
Fault 109
*Call Service*
Earth grounding problem. Make sure RM7838B has earth ground.
Fault 110
*Call Service*
Internal Fault. Configuration jumpers differ from stored values.
Fault 111
*Call Service*
Internal Fault. Relay Module configuration jumper test failure.
Fault 112, 113, 114
*Call Service*
Internal Fault. Relay Module self-test failure.
Fault 115, 116
*Call Service*
Unused
Fault 117 - 121
*Call Service*
Internal Fault. Relay Module self-test failure.
Fault 122
*Call Service*
Unused
Fault 123
*Call Service*
Internal Fault. Relay Module self-test failure.
Fault 124
*Call Service*
Unused.
Fault 125, 126
*Call Service*
Internal Fault. Relay Module self-test failure.
Fault 127
*Call Service*
Internal Fault. Safety relay feedback circuit was in an improper state.
RM7838B
TROUBLESHOOTING
EXPANDED ANNUNCIATOR MESSAGES
(Tables 13 and 14)
If the Expanded Annunciator is wired to the limit con-
trols and interlock controls strings and connected to the
RM7838B, additional hold messages, fault messages or
code numbers will enhance the original hold messages,
fault messages or code numbers. The message will demon-
strate which device opened first in a monitored series string
of limits or interlocks.
Содержание RM7838B Series
Страница 55: ...55 65 0120 1 ...